Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 250 -
4.2.2 Outdoor connecting pipe
Model(kW) Liquid side Gas side Connecting method
10-14 Φ9.53 Φ19 Flare, Digital scroll
28
Φ12.7
Φ28.6
Welding
4.2.3 Dimensions of indoor main pipe (1, 2)
Indoor main pipe
Refrigerant Capacity(kW)
Gas/Liquid
Branch joint
A<16.8 Φ15.9 / Φ9.5 YDSA/FQ01
16.8≤A<22.4 Φ19.1 / Φ9.5
R-410A
22.4≤A<33.0 Φ22.2 / Φ9.5
YDSA/FQ02
4.2.4 Dimensions of indoor connecting pipe (3)
Connecting pipe
Refrigerant Type (A)
Liquid Gas
A≤4.5 kW
Φ6.4 Φ12.7
R-410A
5.6 kW ≤ A
Φ9.5 Φ15.9
4.2.5 Connecting method
10-14 kW
Gas side Liquid side
Outdoor unit Flaring nut Flaring nut
Indoor unit Flaring nut Flaring nut
Branch part Welding Welding
BS device Flaring nut Flaring nut
28 kW
Gas side Liquid side
Outdoor unit Welding Flaring nut
Indoor unit Flaring nut Flaring nut
Branch part Welding Welding