York Floor Ceiling R-410A 50Hz Service Manual Page 188

  • Download
  • Add to my manuals
  • Print
  • Page
    / 385
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 187
Expose & Conceal Floor Standing
___________________________________________________________________________________
- 187 -
YDS-45SC15IA-A YDS-56SC15IA-A YDS-71SC15IA-A YDS-80SC15IA-A
Model
YDS-45SC15IA-B YDS-56SC15IA-B YDS-71SC15IA-B YDS-80SC15IA-B
Power supply V-Ph-Hz
1 Ph- 220-240 V-50 Hz
Nominal Capacity
Capacity kW
4.5 5.6 7.1 8.0
Cooling
Input W
49.0 88.0 130.0 130.0
Capacity kW
5.0 6.3 9.0 9.0
Heating
Input W
49.0 88.0 130.0 130.0
Motor
Input
W
49/40/34 95/77/67 138.5/119/97
Capacitor
μF
1.2 2.5 3
Speed (Hi/Me/Lo)
r/min
820/745/600 915/770/660 1120/1020/880
Coils
a. Number of rows
3 2 3
b. Tube pitch(a)x row pitch(b)
mm
25.4x22
c. Fin spacing
mm
1.8
d. Fin type (code)
Hydrophilic aluminum
Ф9.53
e. Tube outside dia.and type mm
Inner groove tube
f. Coil length x height x width
mm
768 x254 x66 1068 x 254 x 44 1068×66×254
g. Number of circuits
3 4 3
Performance
Air flow (Hi/Me/Lo) m
3
/h 660/542/440 1150/970/830 1380/1100/870 1332/1212/1023
Noise level (Hi/Me/Lo)
dB(A)
39/37/35 41/39/37 43/41/38
Piping size Liquid/ Gas side
mm
Ф6.35/Ф12.7
Ф9.53/Ф15.9
Containerization
Unit (WxHxD) mm
1200×220×625 1500×220×625
Packing (WxHxD) mm
1289X722X312 1589X722X312
Dimensions
Net/Gross weight kg 37/43 44/50
Qty per 20’/40’/40’HQ Pieces 93/190/190 72/151/151
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp.: 27°CDB, 19°CWB, and outdoor temp.:35°CDB, equivalent
ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB, and equivalent ref.
Piping: 8m (horizontal)