Controller
___________________________________________________________________________________
- 324 -
3.4 Set page display:
Set page displays” Set”
Mode display: Pressing MODE button to enter into MODE set, and select circularly between
cooling and state.
Set page displays the address of selected outdoor units and module.
Pressing OK button to confirm all setting and send to the corresponding air-conditioners.
“Successful” or “Unsuccessful” shown in the operation state area indicates whether the
transmission is confirmed or not.
3.4) Malfunction and Protection Code Table
ERROR Code ERROR Contents Description ERROR Code ERROR Contents Description
H3
Outdoor adding
malfunction valid for
host unit
PA Defrost Protection
H2
Outdoor decreasing
malfunction valid for
host unit
P8
Compressor Current
3rd Protection
H1
Net communication
malfunction
P7
Compressor Current
2nd Protection
EF Other malfunction P5
Condenser High Temp.
Protection
E4T4 Temp. Sensor malfunction P4
Discharge Pipe Temp.
Protection
E3T3 Temp. Sensor malfunction P3
Compressor Current 1st
Protection
E2 Sensor malfunction P2
Discharge Low-
pressure Protection
E1 E0
Communication
malfunction Phase
sequence or lack of phase
P1 P0
Discharge High-
pressure Protection
Compressor High
Temp. Protection
PF Other Protection
PE Oil Balance
PD Oil Return