6. YDS insulation work
6.1 Insulation material and thickness
6.1.1 Insulation material
Insulation material should adopt the material, which is able to endure the pipe’s
temperature: no less than 70
o
C in the high-pressure side, no less than 120
o
C in the low-
pressure side (For the cooling type machine, no requirements at the low-pressure side.)
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120
o
C)
Cooling only type---- Polyethylene foam (withstand above 100
o
C)
6.1.2 Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm) Adiabatic material thickness
Φ6.4—Φ25.4
10mm
Φ28.6—Φ38.0
15mm
Refrigerant pipe
Φ38.0—Φ67.0
20mm
Drainage pipe
Inner diameterΦ20—Φ32
6mm
6.2) Refrigerant pipe insulation
6.2.1 Work Procedure
6.2.1.1 Before laying the pipes, the non-jointing parts and non-connection parts should be heat
insulated.
6.2.1.2 After the gas proof test is eligible, the jointing area, expanding area and the flange area
should be heat insulated
6.2.2 Insulation for non-jointing parts and non-connection parts