8.2.2.4.2 Indoors power supply wiring
The minimal dimension of wiring (mm2 ) Manual switch (A)
Creepage
breaker
Item
Model
Power supply
Continuous wire length ≤20m
(≤50m)
Ground wire Capacity Fuse
All indoor units 220V 1N-50/60Hz 2.5 (3.5)
φ1.6mm
30 15
30mA
under
0.1sec
8.2.2.4.3 Outdoors power supply wiring
- Sketch map of outdoor wiring
Manual swi t ch
Gr ounded wi r e
Cr eepage swi t ch
Out door power suppl y
Out door uni t
Gr ounded wi r e
Out door uni t
Out door uni t
Gr ounded wi r e
Out door uni t
Cr eepage swi t ch
Gr ounded wi r e
Manual swi t ch
Manual swi t ch
Manual swi t ch
Cr eepage swi t ch
Cr eepage swi t ch
Di st r i but or
box
Minimum wire diameter(mm2) Manual switch(A)
MODEL Power source
A ( Dimension(m))
(continuous length)
Grounding
Capacity
Fuse
Leakage protector
220-240V 1N 50/60Hz
3×10
10 100 50
10-16kW
380-415V 3N~ 50Hz
5×2.5
10 100 16
28 220/380V 3N~ 50Hz
16(A≤29)
25(29A≤46)
35(46A≤78)
16 60 50
100mA 0.1sec or less
Note: For 56 kW and 84 kW, wiring separately according to 28 kW outdoors power wiring
specification.