Controller
___________________________________________________________________________________
- 323 -
means locked heat.
Fan Speed Display:
means low speed,
means middle speed,
means high speed.
Compressor State Display: “COMP. 1 2 3 4 5 6”
Electromagnetism Valve Display: “EMV. 1 2 3 4 5 6”
4-Way Valve Display St2
Defrost Display: “Defrost”
Oil Return Display: “OIL RETURN”
Page 0 displays the consumption of electric energy with “ELECTRIC ENERGY kWh” and the
number.
Page 1 displays the input power frequency with “Frequency Hz” and the number.
Page 2 displays the total number of indoor units.
Page 3 displays the temperature symbol T3 with “TEMP.
o
C”, “T3” and the number.
Page 4 displays the temperature symbol T4 with “TEMP.
o
C”, “T4” and the number.
Page 5 displays the temperature symbol T6 with “TEMP.
o
C”, “T6” and the number.
Page 6 displays the discharge temperature of compressor symbol C1 with “TEMP.
o
C”, “C1”
and the number.
Page 7 displays the discharge temperature of compressor symbol C2 with “TEMP.
o
C”, “C2”
and the number.
Page 8 displays the discharge temperature of compressor symbol C3 with “TEMP.
o
C”, “C3”
and the number.
Page 9 displays the compressor current symbol 1 with “CURRENT A”, “1” and the number.
Page 10 displays the compressor current symbol 2 with “CURRENT A”, “2” and the number.
Page 11 displays the compressor current symbol 3 with “CURRENT A”, “3” and the number.
Page 12 displays the digital capacity with “DIGITAL CAPACITY” and the number.
Page 13 displays the openness of electromagnetism valve symbol 1 with “VALVE
OPENNESS”,”1” and the number.
Page 14 displays the openness of electromagnetism valve symbol 2 with “VALVE
OPENNESS”,”2” and the number.
Page 15 displays the most advanced malfunction with “MALFUNCTION” and the code.
Page 16 displays the most advanced protection with “PROTECTION” and the code.
NOTE: The page will increase or decrease by 1 every time you press “PAGE UP” or “PAGE
DOWN”. Select the online outdoor unit by push the “previous” or “next” freely.