Outdoor
___________________________________________________________________________________
___________________________________________________________________________________
- 28 -
1. Specification
Outdoor YDS-100-840 WA15/35A R-22 50Hz
Model
YDS-100WC15A YDS-140WC15A YDS-100WC35A YDS-140WC35A YDS-280WC35A
Power supply Ph-V-Hz 1Ph-220-240 V-50 Hz 3 Ph-220-240 V-50 Hz
Nominal capacity
Capacity kW 10.0 14.0 10.0 14.0 29.0
Cooling
Input
kW 3.6 4.2 3.5 4.5 8.9
Capacity kW 12.0 16.0 12.0 16.0 30.0
Heating
Input
kW 3.5 3.9 3.4 4.4 8.7
Electrical parameter
Max. input consumption kW 6.23 6.39 6.78 7.75 12.5
Max. current A 28 30 10 12 21
Starting current A 142 156 64 64 64
Compressor
Capacity Btu/h 50500 14 14 32.2
Rated current (RLA) A 31.4 8.5 8.5 18.5
Thermal protector Inner Internal
Refrigerant oil ml 1890 1800 3600
Motor
Input W 158×2 138*2 700/450
Capacitor uF 5×2 3.5x2 10
Speed r/min 890/590 800 670/450
Coil
a. Number of rows 2 2.5
b. Tube pitch(a)x row pitch(b) mm 25.4×22
c. Fin spacing mm 1.8
d. Fin type (code) Hydrophilic aluminum
mm Ф9.53
e. Tube outside dia.and type
Inner grove copper tube
f. Coil length x height x width mm 715x1220x44 870x980x60
g. Number of circuits 8 10x2
Performance
Air flow m
3
/h 6000 10000
Noise level dB 55 68
Piping connection
Liquid side/ Gas side mm
φ9.53/φ19 φ12.7/φ28.6
Max. Refrigerant pipe length m 50 70 50 70 175
Max. Difference in level m 8 8 8 8 15
Refrigerant charge kg 4.6 4.6 4.1 4.1 11
Containerization
Unit (WxHxD) mm 940x1245x340 997x1830x880
Packing (WxHxD) mm 1058x1300x435 1105x2020x1034
Dimensions
Net/Gross weight
kg 112/125 117/126 245/260
Qty per 20’/40’/40’HQ Pieces 50/100/100 10/20/20
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and
outdoor temperature: 35°CDB, equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor
temperature: 7°CDB, 6°CWB, and equivalent ref. Piping: 8m (horizontal)