- 265 -
this method can’t dry thoroughly. So, please pay more attention to prevent water entering and
forming condensation water.
Vacuum dry for the second time 1h pumping
Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat
procedure and .
Vacuum placing test · 1h
Sketch map of special vacuum dry procedure