4-Way Cassette
___________________________________________________________________________________
- 79 -
Model YDS-71KC15IA YDS-80KC15IA YDS-90KC15IA YDS-112KC15IA YDS-140KC15IA
Power supply Ph-V-Hz 1Ph-220-240V-50Hz
Capacity
Capacity kW 7.1 8 9 11.2
14
Cooling
Input
W 115 115 160 160
180
Capacity kW 8 9 10 12.5
15
Heating
Input
W 115 115 160 160
180
Motor
Input W 120/110/100 165/143/114
204
Capacitor uF 3.5UF/450V 3.5UF/450V
4
Speed (Hi/Me/Lo) r/min 800/670/550 840/770/640
770/640/550
Coil
Number of rows 2
3
Tube pitch(a)x row pitch(b) mm 21x13.37
Fin spacing mm 1.45
1.5
Fin type Hydrophilic Aluminum
Ф7
Tube outside dia. and type mm
Inner groove Tube
Coil length x height x width mm 1959.4x168x26.74
1916x252x40.1
Number of circuits 8
2
Performance
Noise level (Hi/Me/Lo) dB(A) 48/45/42 53/48/45
48/45/43
Air flow (Hi/Me/Lo) m
3
/h 1220/1010/820 1540/1300/1120
1802/1483/1284
Piping size Liquid / Gas side mm Ф9.53/Ф15.9
Containerization
Dimension (WxHxD) mm 840x230x840 840x300x840
Packing (WxHxD) mm 955x247x955 955x317x955
Unit
Net/Gross weight
kg 30/34 36/41
Dimension (WxHxD) mm 950x46x950
Packing (WxHxD) mm 1035x90x1035
Panel
Net/Gross weight
kg 6/9
Qty per 20’/40’/40’HQ Pieces 62/132/135
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB, 19°CWB, and outdoor temp.:35°CDB, equivalent
ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB, and equivalent ref.
Piping: 8m (horizontal)