Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 278 -
8. Electric installations
Electric installation must be carried out according to National Standard.
This chapter is just for reference.
8.1) Brief Introduction
8.1.1 All wires, parts and material must conform to concerning national standards.
8.1.2 All wiring work must be done by qualified person.
8.1.3 Grounded well.
8.2) Power circuitry installation
8.2.1 Sketch map of power wiring
I ndoor / out door uni t communi cat i on wi r e
I ndoor / out door uni t communi cat i on wi r e
Di st r i but or box
Manual swi t ch
Gr ounded wi r e
Cr eepage swi t ch
Out door power suppl y
Manual swi t ch
Cr eepage swi t ch
I ndooor power suppl y
Out door uni t
8.2.2 Selection creep age breaker
8.2.2.1 The creep age protection switch consists of creep age, zero-phase current mutual
inductance and automatic switch. It is applicable to AC 60Hz, single-phase, 220V or three-
phase, 380V. It can prevent person from getting an electric shock and protect device from creep
age. In normal case, it can provide conversion for circuit.
8.2.2.2 Selection creep age breaker
Selecting the creep age breaker according to 1.5-2 times of the sum of loading rated
current.