2.2) Hi wall EXV Integrated YDS-22-56 HC15IA R-410A 50 Hz
Model YDS-22HC15IA YDS-28HC15IA YDS-36HC15IA YDS-45HC15IA YDS-56HC15IA
Power supply Ph-V-Hz 1 Ph-220-240V-50Hz
Nominal capacity
Capacity kW 2.2 2.8 3.6 4.5 5.6
Cooling
Input
W 30.0 30.0 30.0 45.0 45.0
Capacity kW 2.6 3.2 4.0 5.0 6.3
Heating
Input
W 30.0 30.0 30.0 45.0 45.0
Motor
Input W 30/24/22 44/42/39
Capacitor uF 1.2
Speed (Hi/Me/Lo) r/min 880/810/760 1030/980/880
Coil
Number of rows 2
Tube pitch(a)x row pitch(b) mm 21 x13.37
Fin spacing mm 1.5
Fin type Hydrophilic Aluminum
Tube outside dia. and type mm Ф7, Inner groove Tube
Coil length x height x width mm 635x315 x26.74 785x357x26.74
Number of circuits 3 6
Performance
Noise level (Hi/Me/Lo) dB(A) 35/32/29 40/38/34
Air flow (Hi/Me/Lo) m
3
/h 580/500/420 900/760/650
Piping size Liquid side/ Gas side mm
φ6.35/φ12.7 φ9.53/φ15.9
Containerization
Unit (WxHxD) mm 915 x210x290 1070 x210x315
Packing (WxHxD) mm 1020X300X385 1180X300X410
Dimensions
Net/Gross weight
kg 12/16 15/19
Qty per 20’/40’/40’HQ Pieces 312/668/780 288/578/653
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor temperature: 35°CDB,
equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, and
equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat