Unit selection base on cooling load
___________________________________________________________________________________
___________________________________________________________________________________
- 23 -
2.5) Temperature range of operation
Notes: These figures assume the following operation conditions (Indoor and outdoor units):
1. Equivalent pipe length: 10 m
2. Height difference: 0 m
2.6) Example for unit selection with cooling load
1) Given condition
[1] Design condition (Cooling: Indoor 20°C (WB), Outdoor 35°C (DB))
[2] Cooling load
Location Room A Room B Room C Room D Room E Room F
Load (Kw) 2.1 2.8 3.5 4.6 5.8 7.2
[3] Power supply unit: 3 Faze 380V 50Hz
[4] Pipe length: 50m
[5] Height difference: 30m