York Floor Ceiling R-410A 50Hz Service Manual Page 157

  • Download
  • Add to my manuals
  • Print
  • Page
    / 385
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 156
Medium ESP duct
___________________________________________________________________________________
___________________________________________________________________________________
- 156 -
Model YDS-71UC15IA YDS-80UC15IA YDS-90UC15IA YDS-112UC15IA YDS-140UC15IA
Power Supply Ph-V-Hz 1 Ph-220-240 V-50 Hz
Nominal Capacity
Capacity kW 7.1 8.0 9.0 11.2 14.0
Cooling
Input
W 150 150 215 215 215
Capacity kW 8.0 8.4 10.0 12.5 15.0
Heating
Input
W 150 150 215 215 215
Motor
Input W
170/150/133 104/87/78
Capacitor uF
6.5UF/450V 4UF/450V x2
Speed (Hi/Me/Lo) r/min
1100/1020/900 840/695/610
Coil
Number of rows 3
Tube pitch(a)x row pitch(b) mm 25.4X22
Fin spacing mm 1.7
Fin type Hydrophilic Aluminum
Tube outside dia.and type mm Ф9.53 Inner groove Tube
Coil length x height x width mm 800x254x66 1150x254x66
Number of circuits 3 5
Performance
Noise level (Hi/Me/Lo) dB(A)
46/44/42 47/45/43 48/46/44
External static pressure Pa 40 70
Air flow (Hi/Me/Lo) m
3
/h
1400/1100/900 1800/1500/1200
Piping size Liquid/ Gas side mm φ9.5 / φ15.9
Containerization
Unit (WxHxD) mm 1000×298×800 1350×298×800
Packing (WxHxD) mm 1205x370x940 1555x370x940
Dimensions
Net/Gross weight
Kg 37.2/43.3 51.4/58.3
Qty per 20’/40’/40’HQ Pieces 60/140/164 48/100/112
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB,19°CWB,outdoor tem
perature:35°CDB,equivalent ref. Piping: 8m(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature:
7°CDB,6°CWB,equivalent ref. Piping: 8m(horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat