York Floor Ceiling R-410A 50Hz Service Manual Page 131

  • Download
  • Add to my manuals
  • Print
  • Page
    / 385
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 130
Floor & ceiling
___________________________________________________________________________________
- 130 -
Model
YDS-80FC15IA YDS-90FC15IA YDS-112FC15IA YDS-140FC15IA
Power supply Ph-V-Hz 1 Ph- 220-240 V- 50 Hz
Nominal Capacity
Capacity kW 7.9 8.8 11.7 14.1
Cooling
Input W 155 155 240 240
Capacity kW 9.4 10.6 13.2 15.5
Heating
Input W 155 155 240 240
Motor
Input W 130 182
Capacitor uF 3.5uF/450V 2.5 uF /450v
Speed (Hi/Me/Lo) r/min
1310/1200/1000 820/695/620
Coil
Number of rows 3
Tube pitch(a)x row pitch(b) mm 25.4×22
Fin spacing mm 1.7
Fin type (code) Hydrophilic aluminum
Tube outside dia. and type mm Ф9.53 Inner groove tube
Coil length x height x width mm 905x203x66
1150x254x66
Number of circuits 5
Performance
Noise level (Hi/Me/Lo) dB(A)
45/43/40 47/45/42
Air flow (Hi/Me/Lo) m
3
/h
1400/1200/1000 2000/1800/1600
Piping size Liquid/ Gas side mm φ9.5 /φ15.9
Containerization
Unit (WxHxD) mm 1285x660x198 1670x680x240
Packing (WxHxD) mm 1379x744x296 1764x760x329
Dimensions
Net/Gross weight Kg 37/42 54/61
Qty per 20’/40’/40’HQ Pieces 128/270/300 99/203/228
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor temperature: 35°CDB,
equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, and
equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat