- 129 -
2. Specifications
Floor Ceiling YDS-36-112FC15IA/IB R-410 50Hz
Model
YDS-36FC15IA YDS-45FC15IB YDS-56FC15IA YDS-71FC15IA
Power supply Ph-V-Hz 1 Ph- 220-240 V- 50 Hz
Nominal Capacity
Capacity kW 3.5 4.7 5.3 7.0
Cooling
Input W 130 140 140 140
Capacity kW 4.0 5.1 6.2 8.2
Heating
Input W 130 140 140 140
Motor
Input W 120 120
Capacitor uF 1.2uF/450V 2uF/450V
Speed (Hi/Me/Lo) r/min 750/660/590 1280/ 1190/1000
Coil
Number of rows 2 3
Tube pitch(a)x row pitch(b) mm 25.4×22
Fin spacing mm 1.8
Fin type (code) Hydrophilic aluminum
Tube outside dia. and type mm Ф9.53 Inner groove tube
Coil length x height x width mm 804x254x44 804x254x66
Number of circuits 5
Performance
Noise level (Hi/Me/Lo) dB(A)
43/41/38 43/41/38
Air flow (Hi/Me/Lo) m
3
/h
650/570/500 800/600/500
Piping size Liquid/ Gas side mm φ6.4 /φ12.7 φ9.5 /φ15.9
Containerization
Unit (WxHxD) mm 995x660x198
Packing (WxHxD) mm 1089x744x296
Dimensions
Net/Gross weight Kg 29/35
Qty per 20’/40’/40’HQ Pieces 128/270/300
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor temperature: 35°CDB,
equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, and
equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat
Page view 129