York Floor Ceiling R-410A 50Hz Service Manual Page 187

  • Download
  • Add to my manuals
  • Print
  • Page
    / 385
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 186
Expose & Conceal Floor Standing
___________________________________________________________________________________
- 186 -
2. Specifications
Expose Floor-Standing YDS-22-80FC15IA-A/B R-410A 50Hz
YDS-22SC15IA-A YDS-28SC15IA-A YDS-36SC15IA-A
Model
YDS-22SC15IA-B YDS-28SC15IA-B YDS-36SC15IA-B
Power supply V-Ph-Hz
1 Ph- 220-240 V-50 Hz
Nominal Capacity
Capacity kW
2.2 2.8 3.6
Cooling
Input W
40.0 46.0 35.0
Capacity kW
2.6 3.2 4.0
Heating
Input W
40.0 46.0 35.0
Motor
Input
W
42/37/34 49/40/34
Capacitor
μF
0.8 1 1.2
Speed (Hi/Me/Lo)
r/min
935/810/720 820/745/600
Coils
a. Number of rows
2 3
b. Tube pitch(a)x row pitch(b)
mm
25.4x22
c. Fin spacing
mm
1.8
d. Fin type (code)
Hydrophilic aluminum
Ф9.53
e. Tube outside dia.and type mm
Inner groove tube
f. Coil length x height x width
mm
568 x254 x44 768 x254 x66
g. Number of
circuits
3
Performance
Air flow (Hi/Me/Lo) m
3
/h 530/456/400 569/485/421 624/522/375
Noise level (Hi/Me/Lo)
dB(A)
37/35/33 39/37/35
Piping size Liquid/ Gas side
mm
Ф6.35/Ф12.7
Containerization
Unit (WxHxD) mm
1000×220×625 1200×220×625
Packing (WxHxD) mm
1089X722X312 1289X722X312
Dimensions
Net/Gross weight kg 30/35 37/43
Qty per 20’/40’/40’HQ Pieces 119/236/273 93/190/190
Notes:
1 Nominal cooling capacities are based on the following conditions: return air temp.: 27°CDB, 19°CWB, and outdoor temp.:35°CDB, equivalent
ref. piping: 8m (horizontal)
2 Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB, and equivalent ref.
Piping: 8m (horizontal)
Page view 186
1 2 ... 182 183 184 185 186 187 188 189 190 191 192 ... 384 385