6.8 Operating Inspections
By following a regular inspection schedule any potential
problems with the unit can be identified early and
attended to before serious operating difficulties occur.
The following list of inspections and procedures should
be used as a guide. In all cases the inspections should
only be carried out by properly trained personnel. If a
problem is identified, no attempt should be made to
carry out any repairs unless properly qualified and
equipped to do so. Where appropriate, refer to the
control centre Operation Instruction for correct keypad
operation to access data on the control centre display.
Daily
1. Check the bearing oil pressure: The actual
bearing oil pressure will vary with compressor
suction and discharge pressures. When a new
system is first operated under normal full load
conditions, the bearing oil pressure should be
recorded as a reference point with which to
compare subsequent readings.
2. Check Oil Pressure Display: The oil and oil filter
transducers are compared during compressor
operation. If the differential filter pressure exceeds
140 kPa for 5 seconds, the message WARNING -
DIRTY OIL FILTER is displayed. If the differential
filter pressure exceeds 170 kPa for 5 seconds, the
unit shuts down and the displayed message is
CLOGGED OIL FILTER. A gradual decrease in
bearing pressure of 30 to 60 kPa (with constant
suction and discharge pressures) may be an
indication of a dirty filter. The filter should be
replaced when pressure loss is 30% of the original
pressure.
3. Check the oil level in the oil separator reservoir:
The correct oil level is half way up the sight glass
but this may vary depending on load. The level
should not disappear from the sight glass.
4. Check entering and leaving condenser water
temperatures and condenser pressure for
comparison with design conditions.
5. Check the entering and leaving chilled liquid
temperatures and evaporator pressure for
comparison with design conditions.
6. Check the compressor discharge temperature:
During normal operation discharge temperature
should not exceed 100°C
7. Check the compressor motor voltage and
current: At the Electro Mechanical Starter or on the
control centre display for units with a Solid State
Starter.
8. Check for any signs of dirty or fouled condenser
tubes. The temperature difference between water
leaving condenser and liquid refrigerant leaving the
condenser should not exceed the difference
recorded for a new unit by more than 2.2°C.
9. Check water treatment is correct.
10. Any time the control centre display indicates
PRESS STATUS KEY, do so to read any warning
messages to be displayed.
6.9 Operating Log Sheet
An accurate record of system operating conditions
(temperatures and pressures) recorded at regular
intervals throughout each 24 hour operating period
should be kept. An optional status printer is available for
this purpose using automatic data logging after
programming the DATA LOGGER function.
The record of readings serves as a valuable reference
for operating the system. Readings taken when a
system is newly installed will establish normal
conditions with which to compare later readings. A
sample log sheet is provided opposite, listing the
appropriate unit information which should be recorded
regularly.
6.10 Maintenance and Service
Units are not generally user serviceable and no attempt
should be made to rectify any faults found with the unit
unless suitably qualified and equipped to do so. If the
unit is malfunctioning in any manner, or the unit is
stopped by one of the safety controls, consult Section 8.
After repair or adjustment if the compressor cannot be
started or the particular fault continues to affect the
performance of the unit, please call the nearest York
Office. Failure to report recurring problems or continued
operation of a malfunctioning unit may lead to personal
injury or damage to the unit.
6.10.1 Normal and Safety System Shutdowns
Normal and safety system shutdowns have been built
into the unit to protect it from damage during certain
operating conditions. The unit will be stopped
automatically by controls that respond to high
temperatures, low temperatures, and low and high
pressures, etc. These safety shutdowns require the
operator to manually reset the control centre prior to
restarting the unit.