The control centre includes unique safety logic to
protect the unit from damaging malfunctions.
Comprehensive information can be displayed in the
event of a unit shutdown including day, time, and reason
for shutdown. Reasons include high condenser
pressure, low oil pressure at compressor, clogged oil
filter, low oil level in oil separator, high oil temperature,
high oil pressure, high compressor discharge
temperature, low evaporator pressure, motor controller
fault, and sensor malfunction.
Background messages are displayed while the unit is
running to inform of any controlling conditions such as:
current limit in effect, low pressure limit in effect, high
pressure limit in effect, leaving chilled water
temperature control, and non-critical sensor error.
System cycling messages are displayed in regard to
day, time, cause of cycling shutdown, and auto start
indication. These include low water temperature,
evaporator/condenser water flow interruption, internal
time clock, and anti-recycle.
Digital programming of operating setpoints from the
keypad include leaving chilled water temperature,
current limiting, pulldown demand limiting, daily
start/stop scheduling of chiller, pumps and tower, and
separate holiday schedule.
Individual LED indicators highlight slide valve loading/
unloading/auto control, program mode, and display
hold.
Manual operation of slide valve loading and unloading is
provided through separate buttons in the service section
of the keypad.
All operating and setpoint information can be
transmitted to a remote printer through the RS-232 port
in the control centre to obtain data logs. This can be
accomplished at any time by pressing the "Print" button
on the control centre keypad, or automatically at
predetermined intervals by programming the panel.
The remote printer will also record time and cause of any
safety or cycling shutdown and a history of the last four
shutdowns.
The control centre is compatible with remote Building
Automation Systems (BAS) and Energy Management
Systems (EMS). The remote control functions available
as standard include start and stop, leaving chilled water
temperature reset and current limit reset through PWM
signal, and "ready to start", "safety" and "cycling"
shutdown status contacts. Further remote control
features are available via an optional York ISN
translator.
2.15 Options and Accessories
Motor Starter
The solid state starter is a reduced voltage starter that
controls and maintains a constant current flow to the
motor during start-up. It is compact and mounted on the
unit adjacent to the motor terminals. Power and control
wiring is factory supplied. The starter enclosure is IP33
rated with a hinged access door with lock and key.
Standard features include: digital readout at the control
centre of 3-phase voltage and current; high and low line
voltage protection; 115 V control transformer; three-leg
sensing overloads; phase rotation and single-phase
failure protection; and momentary power interruption
protection. An integral door interlocked and
pad-lockable fused disconnect switch is also available.
BAS/EMS Remote Control Interface
A communication interface permitting complete
exchange of unit data with any BAS/EMS is available via
an optional ISN translator. The ISN translator also
allows a BAS/EMS to issue commands to the unit to
control its operation. ISN translators are available in two
models for controlling up to four, or up to eight units.
Remote Reset Controls
Optional PCB to allow reset of leaving chilled water
temperature and percent motor current limit by a BAS/
EMS using 4-20 mA, 0-10 Vdc, or discrete stepped
signals rather than the standard pulse width modulated
(PWM) signal requirement.
Factory Insulation of Evaporator
Factory-applied 19 mm thick anti-sweat insulation
(flexible, closed-cell plastic type) is attached with
vapour-proof cement to the evaporator shell, flow
chamber, evaporator tube sheets, suction connection,
and (as necessary) to the auxiliary tubing. This
insulation will normally prevent sweating in
environments with relative humidity up to 75% and dry
bulb temperatures ranging from 10°Cto32°C. 38 mm
thick insulation is also available for environments with
relative humidity up to 90% and dry bulb temperatures
ranging from 10°Cto32°C. Insulation of water boxes
and nozzles is not included.