Page view 22
3.4 Rigging
The complete standard unit is shipped without skids.
(When optional skids are used it may be necessary to
remove the skids so riggers skates can be used under
the unit end sheets to reduce overall height.)
Each unit has four (4) lifting holes (two in each end) in
the end sheets which should be used to lift the unit.
Care should be taken at all times during rigging and
handling of the chiller to avoid damage to the unit and its
external connections. Lift only using holes shown.
Do not lift the unit with slings around
motor/compressor assembly or by means of
eye bolts in the tapped holes of the
compressor motor assembly. Do not turn a
unit on its side for rigging. Do not rig vertically.
The rigging and operating weights and overall
dimensions are given in Section 9 as a guide in
determining the clearances required for rigging. (Add
150 mm to overall height for optional skidded unit.).
035L02381-GB0 3-3
Figure 3.1Rigging