York YS Service Manual Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
6.4 Normal Operation
After the compressor reaches its operating speed the
slide valve will begin to load, under the control of the
control Centre, based on the leaving chilled liquid
temperature. The unit capacity will vary to maintain the
leaving chilled liquid temperature at the programmed
setpoint. A drop in chilled liquid temperature will cause
the slide valve to unload to decrease unit capacity.
When the chilled liquid temperature rises, the slide valve
loads the compressor and increases the unit capacity.
The compressor motor current will be limited to a
programmable maximum during the unit operation. The
control centre can be programmed in various ways to
limit the motor current to between 40 and 100% of Full
Load Current as required (see the control centre
Operation Instruction for more details).
While the compressor is running a wide variety of
system parameters are monitored automatically by the
control centre. These can be accessed and displayed as
required via the control centre keypad and display. If any
problems are detected the cause will be shown on the
display and the appropriate action will be taken, eg
reducing slide valve loading, giving a warning message,
or shutting down the unit.
6.5 Shutdown
During normal operation the unit may shut down for a
number of reasons such as low load, scheduled daily
shutdowns and multi unit cycling. In each case the
control centre display will indicate the reason for the
shutdown. For example, if during operation the control
centre has unloaded the compressor completely and
load continues to fall, the unit will be shut down and the
display will read: DAY-TIME - LOW WATER
TEMPERATURE - AUTOSTART.
This occurs when the leaving water temperature falls to
2.2°C below setpoint or 2.2°C, whichever is higher.
"Autostart" indicates that the unit will restart
automatically if the water temperature rises again.
If the unit is shut down because a problem has been
detected by the control centre, a similar type of message
will be displayed indicating the nature of the problem
(see control centre Operation Instruction, for more
information).
When the unit is shutdown, the slide valve will close
automatically to minimise load on the compressor motor
during startup. A minimum of two minutes after
shutdown is required for system pressure equalisation
before the compressor will be allowed to restart.
6.6 Manual Shutdown
To stop the unit manually:
1. Push the COMPRESSOR "STOP/RESET" switch.
The control centre display will show: 2.0 MIN.
LOCKOUT DELAY. This prevents compressor
restart until system equalization is achieved.
2. Stop the chilled water pump (if not wired into the
control centre, in which case it will shut off
automatically.)
3. Open the switch to the cooling tower fan motors, if
used.
The compressor sump oil heater
(thermostatically controlled) is energised
when the unit is stopped.
6.7 Prolonged Shutdowns
If the unit is to be shut down for an extended period of
time (for example, over the winter season), the following
procedure should be followed:
1. If freezing temperatures are likely to be
encountered while the system is idle, carefully
drain the cooling water from the cooling tower,
condenser, condenser pump, and the chilled water
system, chilled water pump and cooler. Open the
drains on the cooler and condenser liquid heads to
assure complete drainage. If a Solid State Starter is
fitted drain water from starter cooling loop.
2. Move jumper J-57 on the microprocessor board to
the OFF position to conserve the battery (see
control centre Operation Instruction).
3. Open the main disconnect switches to the
compressor motor, condenser water pump and the
chilled water pump. Open the 115 Vac circuit to the
control centre.
To return the unit to operation is the reverse of this
procedure, however, after a prolonged shutdown it will
be necessary to replace all of the oil and install a new oil
filter element. This should only by done by suitably
qualified personnel.
6-2 035L02381-GB0
Page view 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 67 68

Comments to this Manuals

No comments