York YS Service Manual Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
3. Open the oil charging valve and pump oil into the
system until oil level in the oil separator is about
midway in the upper sight glass. Then, close the
charging valve and disconnect the hand oil pump.
4. As soon as oil charging is complete, close the
power supply to the starter to energise the oil
heater. This will keep the concentration of
refrigerant in the oil to a minimum.
Draining the oil
1. If the oil draining is to restore the correct oil level the
unit may be kept in operation. If the oil charge is
being replaced the unit must be shut down and the
supply switched off to prevent operation of the oil
heater.
2. If possible run the unit at full load for a short period
to recover most of the oil in the system to the oil
separator.
3. Drain the oil into a suitable container from the oil
charging valve on the bottom of the oil separator.
4. Dispose of old oil according to local regulations for
the disposal of oily wastes.
7.6 Refrigerant Charge
The refrigerant system is pressure tested and
evacuated at the factory.
7.6.1 Checking The Refrigerant Charge
The refrigerant level should have been observed
and the level recorded after initial charging. With
the correct charge the level should visible in the
sight glass.
The refrigerant charge should always be
checked and trimmed when the system is shut
down.
The refrigerant charge level must be checked after the
pressure and temperature have equalised between the
condenser and cooler. This would be expected to be 4
hours or more after the compressor and water pumps
are stopped.
7.6.2 Leak Testing
After the system has been charged, the system should
be carefully leak tested with a R134a compatible leak
detector to ensure all joints are tight.
If any leaks are indicated, they must be repaired
immediately. Usually, leaks can be stopped by
tightening flare nuts or flange bolts. However, for any
major repair, the refrigerant charge must be removed.
7.6.3 Vacuum Testing
Vacuum testing should be conducted as follows:
1. Connect a high capacity vacuum pump, with
indicator, to the system charging valve and start the
pump.
2. Open wide all system valves. Be sure all valves to
the atmosphere are closed.
3. Operate the vacuum pump until a wet bulb
temperature of 0°C or a pressure of 5 mm Hg
(absolute) is reached.
4. To improve evacuation circulate warm water (not to
exceed 50°C) through the cooler and condenser
tubes to thoroughly dehydrate the shells. If a
source of hot water is not readily available, a
portable water heater should be employed. DO
NOT USE STEAM. A suggested method is to
connect a hose between the source of hot water
under pressure and the cooler head drain
connection, out the cooler vent connection, into the
condenser head drain and out the condenser vent.
To avoid the possibility of causing leaks, the
temperature should be brought up slowly so that
the tubes and shell are heated evenly.
5. Close the system charging valve and the stop valve
between the vacuum indicator and the vacuum
pump. Then disconnect the vacuum pump leaving
the vacuum indicator in place.
6. Hold the vacuum in the system for 8 hours; the
slightest rise in pressure indicates a leak or the
presence of moisture, or both. If, after 8 hours the
wet bulb temperature in the vacuum indicator has
not risen above 4.4°C or a pressure of 6.3 mm Hg,
the system may be considered tight.
Be sure the vacuum indicator is valved off while holding
the system vacuum and be sure to open the valve
between the vacuum indicator and the system when
checking the vacuum after the 8 hour period.
7. If the vacuum does not hold for 8 hours within the
limits specified, the leak must be found and
repaired.
7-4 035L02381-GB0
Page view 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 67 68

Comments to this Manuals

No comments