4.21.4 Multi Unit Sequence Connections
(MUS - TB2: Terminals 1 & 9)
For multiple unit installation applications, Multi Unit
Sequence connections are available to start and stop
each unit. The maintained closure of remote contacts
will permit the unit to operate in all operating modes with
the "COMPRESSOR" switch in the "RUN" position.
Conversely, an opening of the contacts will inhibit the
unit from operating.
4.21.5 Manual Reset Overload
(EMS MRO - TB5, terminals 1 & 53)
Connect these contacts to the manual reset overloads
and/or safety devices in the electro mechanical starter.
An opening of the contacts causes the system to
shutdown.
To restart the chiller, reset the external device in the
starter and the unit will automatically restart.
4.21.6 Auxiliary Safety Shutdown
(ASSI - TB5, terminals 1 & 31)
Momentary or maintained closure of a normally open
switch or relay contacts will cause the unit to shutdown.
The unit will not restart until the contacts open and a
manual reset and restart of the unit is carried out.
4.21.7 Remote Leaving Chilled Water Temperature
Setpoint Reset (RLCWTSP - TB2: terminals.1 & 19)
The locally programmed leaving chilled water
temperature setpoint can be reset bya1to11second
timed closure of remote contacts connected to these
terminals. The signal will only be accepted when the
control centre is in the "REMOTE" operating mode.
An accepted signal will adjust the leaving chilled water
temperature up to 11°C upwards from the locally
programmed value. Unit capacity will be adjusted to
achieve the new setting of leaving chilled water
temperature, providing the compressor motor current is
below the current limit setpoint.
A one-second pulse corresponds to no offset and
therefore no adjustment of the preprogrammed leaving
chilled liquid temperature setpoint. An eleven second
pulse corresponds to the locally preprogrammed
maximum allowable offset (5.5'C or 11.1'C) above the
leaving chilled water temperature setpoint. The amount
of offset varies linearly with pulse-width.
An EMS / BAS interface card option is available to allow
remote reset of the leaving water temperature setpoint
using a 4 to 20 mAdc. current signal, a 0 to 1O Vdc
signal, or a single contact closure.
4.21.8 Remote Current Limit Setpoint
(RCSP - TB2: Terminals 1 & 20)
The motor current limit setpoint can be adjusted
remotely bya1to11second timed closure of remote
contacts connected to these terminals. The input signal
will only be accepted when the control centre is in the
"REMOTE" operating mode. An accepted signal will set
the motor current between 100% and 40% of full load
amps. Unit capacity control will remain from the leaving
chilled water temperature, providing the current limit
setpoint is satisfied. If the compressor motor current
exceeds the current limit setpoint, it will override the
temperature control system to reduce unit capacity.
A one-second pulse corresponds to 100% full load
amperes and an eleven-second pulse corresponds to
40% of full load amperes. The current limit setpoint
varies linearly from 100% to 40% as the pulse-width
changes from 1 to 11 seconds.
An EMS / BAS interface card option is available to allow
remote adjustment of the Current Limit setpoint using a
4 to 20 mAdc. current signal, a 0 to 1O Vdc signal, or a
single contact closure.
4.22 Status Connections
Wiring to the status volt free contacts requires a supply
provided by the customer. Particular care must be taken
deriving the supplies for the volt free terminals with
regard to a common point of isolation. These circuits
when used must be fed via the common point of isolation
so that the voltage is removed when the common point
of isolation to the unit is opened.
In accordance with EN 60204 it is
recommended that the customer wiring to
these terminals uses orange wires. This
will ensure that circuits not switched off by
the unit supply disconnecting device are
distinguished by colour so that they can
easily be identified as live even when the
unit disconnecting device is off.
Unless otherwise stated the volt-free contacts
are rated at 5 amps resistive at 250 Vac and
30 Vdc, 2 amp inductive (0.4 pf) at 250 Vac
and 30 Vdc. All inductive devices (relays)
switched by the volt-free contacts must have
their coil suppressed using standard R/C
suppressors.
4-10 035L02381-GB0