3 TRANSPORTATION, RIGGING AND STORAGE
3.1 General
YS units are shipped as a single factory assembled,
piped, wired package, requiring minimum installation to
make chilled water connections, condenser water
connections, refrigerant atmospheric relief connections,
and electrical power connections.
Units can also be shipped dismantled when required by
rigging conditions, but generally it is more economical to
enlarge access openings to accommodate the factory
assembled unit. Units shipped dismantled MUST be
field assembled under the supervision of a York
representative.
FIELD ASSEMBLED UNITS ONLY
Use Form 160.47-N3.1 in conjunction with this manual.
This instruction will be furnished with all units that are to
be field assembled.
A York authorised representative must check the
installation, supervise the initial start-up and operation
of all newly installed units.
The York Warranty may be voided if the
following restrictions are not adhered to:
1. No valves or connections should be opened under
any circumstances because such action will result
in loss of the factory nitrogen charge.
2. Do not dismantle or open the unit for any reason
except under the supervision of a York
representative.
3. When units are shipped dismantled, notify the
nearest York office in ample time for a York
representative to supervise rigging the unit to its
operating position and the assembly of
components.
4. Do not make final power supply connections to the
compressor motor, solid state starter or control
centre.
5. Do not charge the compressor with oil.
6. Do not charge the unit with refrigerant.
7. Do not attempt to start the system.
8. Do not run hot water (40°C maximum.) or steam
through the cooler or condenser at any time.
3.2 Shipment
The unit may be ordered and shipped in any of the
following forms:
Form 1 – Factory Assembled Unit (complete with
motor, refrigerant and oil charges)
1. The motor/compressor assembly mounted, with all
necessary interconnecting piping assembled.
Control centre is mounted on the unit. Complete
unit factory leak tested, evacuated and charged
with R134a.
An optional Solid State Starter can be factory
mounted and wired.
2. Miscellaneous material Four (4) vibration
isolation pads (or optional spring isolators and
brackets).
Form 2 – Factory Assembled Unit (complete with
motor, refrigerant and oil charges shipped separately).
1. The motor/compressor assembly mounted, with all
necessary interconnecting piping assembled.
Control centre is mounted on the unit. Complete
unit factory leak tested, evacuated and charged
with holding charge of nitrogen.
An optional Solid State Starter can be factory
mounted and wired.
2. Miscellaneous material Four (4) vibration
isolation pads (or optional spring isolators and
brackets).
035L02381-GB0 3-1