542300-YIM-A-1009
Johnson Controls Unitary Products 23
060
(5.0)
208-1-60 26.2 150.0 41.0 2.3 7.6 10.0
None - - - 52.7 70
E05 4.0 1 19.2 52.7 70
E07 5.6 1 26.9 55.7 70
E10 8.0 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60 26.2 150.0 41.0 2.3 7.6 10.0
None - - - 52.7 70
E05 5.3 1 23.0 52.7 70
E07 7.5 1 32.6 61.1 70
E10 10.6 1 46.1 77.2 80
E15 15.9 2 69.1 104.8 110
E20 21.2 2 92.2 132.4 150
E30 29.6 2 128.7 176.2 200
208-3-60 17.6 120.0 27.5 2.3 5.2 10.0
None - - - 39.5 50
E05 4.0 1 11.1 39.5 50
E07 5.6 1 15.5 39.5 50
E10 8.0 1 22.2 46.8 50
E15 11.9 2 33.0 60.3 70
E20 15.9 2 44.1 74.2 80
E30 22.2 2 61.6 96.0 100
230-3-60 17.6 120.0 27.5 2.3 5.2 10.0
None - - - 39.5 50
E05 5.3 1 13.3 39.5 50
E07 7.5 1 18.8 41.6 50
E10 10.6 1 26.6 50.9 60
E15 15.9 2 39.9 66.8 70
E20 21.2 2 53.2 82.7 90
E30 29.6 2 74.3 108.0 110
460-3-60 8.3 70.0 13.0 1.3 2.6 5.0
None - - - 19.3 25
E07 6.8 1 8.5 19.7 25
E10 10.1 1 12.7 24.7 25
E15 13.6 2 17.1 29.9 30
E20 19.5 2 24.5 38.8 40
E30 28.8 2 36.1 52.8 60
575-3-60 7.4 53.0 11.5 1.3 2.0 4.0
None - - - 16.3 20
E10 10.6 1 10.6 20.2 25
E15 15.9 1 16.0 26.6 30
E20 21.2 2 21.3 33.0 35
E30 30.4 2 30.5 44.1 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 - With Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps