Figure 29: ZF060 (5.0 Ton) Operating Pressures
Gas Heat Troubleshooting Guide
Before beginning symptomatic troubleshooting activities read
the flash code LEDs on the unit control board (UCB) and the
ignition control board (ICB). Fault codes have a quick sequence
of flashes indicating the flash code number followed by a pause
with the LED off. The ICB flash codes are repeated until the
fault is cleared. The ICB monitors itself, the centrifugal switch,
lockout due to > 16 pilot flame losses, primary limit, rollout and
a flame present when the ICB expects no flame.
With power applied to the unit, if the LED on the ICB is flashing
the heartbeat and the furnace will not operate, then proceed to
the symptomatic troubleshooting section. If the ICB LED is not
flashing, then perform the ICB troubleshooting procedures. If the
ICB has a flash code other than the heartbeat, then determine
the flash code and locate its troubleshooting procedures in the
flash code troubleshooting section. Refer to Table 26 for flash
code identification and component causing fault.
230
280
330
380
430
480
530
105 110 115 120 125 130 135 140 145 150 155 160
Discharge Pressure (psi)
Suction Pressure (psi)
5 Ton Charging Chart
115º
105º
95º
85º
75º
Outdoor Temp (ºF)
Note: Make sure that condenser fan is running when charging.
65º
Troubleshooting of components may require opening
the electrical control box with the power connected to
the unit. Use extreme care when working with live
circuits! Check the unit nameplate for the correct line
voltage and set the voltmeter to the correct range before
making any connections with line terminals.
When not necessary, shut off all electric power to the
unit prior to any of the following maintenance
procedures so as to prevent personal injury.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation, which could cause injury to person
and/or damage unit components. Verify proper
operation after servicing.
The furnace may shut down on a high temperature
condition during the procedure. If this occurs, the UCB
energize the supply air blower motor until the high
temperature limit has reset. Caution should be used at
all times as the supply air blower may energize
regardless of the room thermostat fan switch position.