Table 13: ZF Blower Performance Side Duct
ZF036 (3 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
800 634 0.34 735 0.39 828 0.45 914 0.52 995 0.59 1070 0.67 1140 0.75 1207 0.83 1270 0.92 1332 1.00
1000 659 0.39 760 0.45 853 0.51 939 0.57 1019 0.65 1094 0.72 1165 0.80 1232 0.89 1295 0.97 1356 1.06
1200 685 0.47 786 0.52 879 0.58 965 0.65 1045 0.72 1120 0.80 1191 0.88 1258 0.96 1321 1.05 1382 1.13
1400 716 0.57 816 0.62 909 0.68 995 0.75 1076 0.82 1151 0.90 1221 0.98 1288 1.06 1352 1.15 1413 1.23
1600 752 0.69 852 0.75 945 0.81 1032 0.88 1112 0.95 1187 1.03 1258 1.11 1324 1.19 1388 1.27 1449 1.36
FS
4
ZF048 (4 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1000 703 0.39 786 0.47 866 0.54 942 0.62 1016 0.71 1087 0.79 1155 0.88 1221 0.98 1284 1.07 1345 1.17
1200 733 0.44 817 0.52 896 0.60 973 0.68 1047 0.76 1118 0.85 1186 0.94 1252 1.03 1315 1.12 1376 1.22
1400 770 0.52 853 0.60 933 0.67 1010 0.76 1083 0.84 1154 0.93 1222 1.02 1288 1.11 1352 1.20 1413 1.30
1600 811 0.64 895 0.71 974 0.79 1051 0.87 1125 0.96 1196 1.04 1264 1.13 1330 1.23 1393 1.32 1454 1.42
1800 857 0.80 940 0.87 1020 0.95 1097 1.03 1171 1.11 1242 1.20 1310 1.29 1375 1.38 1439 1.48 1500 1.58
2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.77
FS
4
ZF060 (5 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1200 733 0.44 817 0.52 896 0.60 973 0.68 1047 0.76 1118 0.85 1186 0.94 1252 1.03 1315 1.12 1376 1.22
1400 770 0.52 853 0.60 933 0.67 1010 0.76 1083 0.84 1154 0.93 1222 1.02 1288 1.11 1352 1.20 1413 1.30
1600 811 0.64 895 0.71 974 0.79 1051 0.87 1125 0.96 1196 1.04 1264 1.13 1330 1.23 1393 1.32 1454 1.42
1800 857 0.80 940 0.87 1020 0.95 1097 1.03 1171 1.11 1242 1.20 1310 1.29 1375 1.38 1439 1.48 1500 1.58
2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.77
2200 960 1.24 1043 1.31 1123 1.39 1199 1.47 1273 1.55 1344 1.64 1412 1.73 1478 1.82 1541 1.92 1602 2.01
2400 1015 1.51 1099 1.59 1178 1.66 1255 1.74 1329 1.83 1400 1.92 1468 2.01 1534 2.10 1597 2.19 1658 2.29
2600 1074 1.83 1157 1.90 1237 1.98 1314 2.06 1387 2.14 1458 2.23 - - - - - - - -