York W)036 THRU 060 Specifications Page 55

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 54
542300-YIM-A-1009
Johnson Controls Unitary Products 55
not clean, then clean, reinstall and adjust pilot per the start
up procedures.
2. If the flame is weak or unstable in the flame sensor area,
then verify the gas inlet pressure. If gas inlet pressure is
above the minimum inlet pressure stated on unit data label,
then adjust the pilot pressure per the start up procedures. If
the pilot cannot be adjusted to obtain a strong and stable
flame in the flame sensor area, then remove the burner
assembly and verify the pilot burner assembly is open
internally and the holes in the burner are clean. Check the
pilot orifice size to the unit data plate and the cleanliness of
the pilot orifice. Verify that the flame sensor electrode is
clean and is adjusted properly. After cleaning or
replacement of the pilot assembly components, reinstall the
burner assembly and adjust pilot per the start up procedure.
Primary or Aux Temperature Limit
The temperature limits limit the temperature in the furnace to a
safe level. If a temperature higher than the preset limit is
achieved due to low or no air flow through the furnace, then the
temperature limits opens and the ICB closes the gas valve and
flashes code 6. The primary limit is automatic reset type while
the auxiliary limit is manual reset type. If either one opens, then
the ICB removes power to the gas valve and the UCB
energizes the indoor blower until the primary limit automatically
resets or the auxiliary limit is manually reset. Verify adequate air
flow through the furnace. If air flow is nonexistent or weak, then
troubleshoot and repair the conditioned space air circulation
system as necessary. Reset the auxiliary limit and verify proper
operation of the furnace. If airflow is normal, then verify the gas
input rate to the furnace following the start up procedures
(auxiliary limit must be reset before the furnace will operate). If
after verifying the circulating air system, the input rate to the
furnace and that the air temperature rise through the furnace is
within the rise range on the unit data plate the flash code still
exists, then set the gas valve to the off position and temporarily
apply control voltage (~24 volts) to pin 9 of the 9 pin ICB
connector. With power applied to the unit, if the ICB LED
continues to flash a code 6, then replace the ICB and return unit
to operation (you must remove the temporary voltage to pin 9
before the gas valve is turned on). If the ICB LED flashes a
heartbeat, then replace the limit that is opening, remove the
temporary voltage applied to pin 9, turn on the gas valve, restart
the furnace and verify proper operation of the furnace.
Rollout Switch
The rollout switch is installed to protect the furnace from
damage due to excessive heat in the burner area. There are 4
main reasons the rollout switch will open (flash code 7) due to
excessive heat in the burner area. You must remove power to
the unit for 20 seconds to reset the ICB.
1. A blocked flue outlet is the most common cause for the
rollout switch to open. Check the flue outlet for debris and
clear if necessary.
2. Loose blower wheel on draft motor. Verify that the blower
wheel is securely fastened to the draft motor shaft.
3. Unit operating outside the air temperature rise range stated
on the unit data plate. Either the air flow through the
furnace is not sufficient or the gas input rate to the furnace
exceeds the recommended rate. Verify both conditions are
within the published ranges.
4. Cracked heat exchanger tube(s). If a heat exchanger tube or
tubes is cracked, then the flow through the heat exchanger
is restricted and the flame will either roll out of the tube inlet
or heat will build to an abnormal level in the burner area.
This can usually be determined by observing burner flame
with and without indoor blower operation. If the flame
changes when the blower is running compared to when it is
not, then visually inspect the heat exchanger tubes.
If all of the above are found to be in good condition or within the
operating ranges, then set the gas valve to the off position and
temporarily apply control voltage (~24 volts) to pin 6 of the 9 pin
ICB connector. With power applied to the unit, if the ICB LED
continues to flash a code 7, then replace the ICB and return unit
to operation (you must remove the temporary voltage to pin 6
before the gas valve is turned on). If the ICB LED flashes a
heartbeat, then replace the rollout switch, remove the
temporary voltage applied to pin 6, turn on the gas valve, restart
the furnace and verify proper operation of the furnace.
Unexpected Flame Presence
If a flame is present without a call for heat (flash code 8), then
the ICB will continue operation of the draft motor and the UCB
will call for indoor operation when either of the temperature limit
opens. If the unit is correctly wired and there is not a call for
heat, then check for control voltage to the gas valve. If control
voltage exists at the gas valve, then replace the ICB. If voltage
is not present at the gas valve, then replace the gas valve.
Gas Valve Stuck Off or On
If the pilot and/or the main valves are sensed to be off more
than 1 second when commanded to be on, the control will shut
off all outputs and enter a hard lockout (flash code 9). Likewise,
if the pilot and/or the main valves are sensed to be on more
than 1 second when commanded to be off, the control will shut
off all outputs and enter a hard lockout (flash code 9). The
control will not respond to thermostat demands during a hard
lockout. The only way to recover from a hard lockout is to
remove and reapply 24VAC power to the control.
Flame Sense Circuit Failure
If the control detects an internal hardware failure in the flame
sense circuit, it shuts off all outputs and enters a hard lockout
(flash code 10). The control will not respond to thermostat
demands during a hard lockout. The only way to recover from a
hard lockout is to remove and reapply 24VAC power to the
control. If problem persists after removal and reapplication of
24VAC power, the board may need to be replaced.
Symptomatic Troubleshooting
On calls for heating, the draft motor operates and the furnace
lights but the supply air blower motor does not energize after a
Page view 54
1 2 ... 50 51 52 53 54 55 56 57 58

Comments to this Manuals

No comments