542300-YIM-A-1009
Johnson Controls Unitary Products 25
060
(5.0)
208-3-60 17.6 120.0 27.5 2.3 8.2 10.0
None - - - 42.5 60
E05 4.0 1 11.1 42.5 60
E07 5.6 1 15.5 42.5 60
E10 8.0 1 22.2 50.5 60
E15 11.9 2 33.0 64.0 70
E20 15.9 2 44.1 77.9 80
E30 22.2 2 61.6 99.8 100
230-3-60 17.6 120.0 27.5 2.3 8.2 10.0
None - - - 42.5 60
E05 5.3 1 13.3 42.5 60
E07 7.5 1 18.8 45.3 60
E10 10.6 1 26.6 54.6 60
E15 15.9 2 39.9 70.6 80
E20 21.2 2 53.2 86.5 90
E30 29.6 2 74.3 111.8 125
460-3-60 8.3 70.0 13.0 1.3 4.1 5.0
None - - - 20.8 25
E07 6.8 1 8.5 21.6 25
E10 10.1 1 12.7 26.6 30
E15 13.6 2 17.1 31.8 35
E20 19.5 2 24.5 40.7 45
E30 28.8 2 36.1 54.7 60
575-3-60 7.4 53.0 11.5 1.3 3.6 4.0
None - - - 17.9 25
E10 10.6 1 10.6 22.2 25
E15 15.9 1 16.0 28.6 30
E20 21.2 2 21.3 35.0 35
E30 30.4 2 30.5 46.1 50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 With Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps