542300-YIM-A-1009
52 Johnson Controls Unitary Products
Normal Operating Pressures
Figure 27: ZF036 (3.0 Ton) Operating Pressures
Figure 28: ZF048 (4.0 Ton) Operating Pressures
210.0
260.0
310.0
360.0
410.0
460.0
100 105 110 115 120 125 130 135 140 145 150 155 160 165
Discharge Pressure (psi)
Suction Pressure (psi)
3 Ton Charging Chart
115º
105º
95º
85º
75º
Outdoor Temp (ºF)
1. Make sure that condenser fan is running when charging.
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV's have
been adjusted in the field, The charging chart may no longer apply.
65º
220
270
320
370
420
470
520
105 110 115 120 125 130 135 140 145 150 155 160
Discharge Pressure (psi)
Suction Pressure (psi)
4 Ton Charging Chart
115º
105º
95º
85º
75º
Outdoor Temp (ºF)
1. Make sure that condenser fan is running when charging.
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV's have been
adjusted in the field, The charging chart may no longer apply.
65º
115º
105º
95º
85º
75º
65º