York W)036 THRU 060 Specifications Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
542300-YIM-A-1009
Johnson Controls Unitary Products 21
060
(5.0)
208-1-60 28.8 145.0 45.0 2.3 7.6 0.0
None - - - 45.9 60
E05 4.0 1 19.2 45.9 60
E07 5.6 1 26.9 45.9 60
E10 8.0 1 38.5 57.6 70
E15 11.9 2 57.2 81.0 90
E20 15.9 2 76.4 105.1 110
E30 22.2 2 106.7 142.9 150
230-1-60 28.8 145.0 45.0 2.3 7.6 0.0
None - - - 45.9 60
E05 5.3 1 23.0 45.9 60
E07 7.5 1 32.6 48.6 60
E10 10.6 1 46.1 64.7 70
E15 15.9 2 69.1 92.3 100
E20 21.2 2 92.2 119.9 125
E30 29.6 2 128.7 163.7 175
208-3-60 17.6 123.0 27.5 2.3 7.6 0.0
None - - - 31.9 40
E05 4.0 1 11.1 31.9 40
E07 5.6 1 15.5 31.9 40
E10 8.0 1 22.2 37.3 45
E15 11.9 2 33.0 50.8 60
E20 15.9 2 44.1 64.7 70
E30 22.2 2 61.6 86.5 90
230-3-60 17.6 123.0 27.5 2.3 7.6 0.0
None - - - 31.9 40
E05 5.3 1 13.3 31.9 40
E07 7.5 1 18.8 32.1 40
E10 10.6 1 26.6 41.4 45
E15 15.9 2 39.9 57.3 60
E20 21.2 2 53.2 73.2 80
E30 29.6 2 74.3 98.5 100
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 Without Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
Page view 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 57 58