York W)036 THRU 060 Specifications Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
542300-YIM-A-1009
Johnson Controls Unitary Products 19
060
(5.0)
208-3-60 17.6 120.0 27.5 2.3 8.2 0.0
None - - - 32.5 40
E05 4.0 1 11.1 32.5 40
E07 5.6 1 15.5 32.5 40
E10 8.0 1 22.2 38.0 50
E15 11.9 2 33.0 51.5 60
E20 15.9 2 44.1 65.4 70
E30 22.2 2 61.6 87.3 90
230-3-60 17.6 120.0 27.5 2.3 8.2 0.0
None - - - 32.5 40
E05 5.3 1 13.3 32.5 40
E07 7.5 1 18.8 32.8 40
E10 10.6 1 26.6 42.1 50
E15 15.9 2 39.9 58.1 60
E20 21.2 2 53.2 74.0 80
E30 29.6 2 74.3 99.3 100
460-3-60 8.3 70.0 13.0 1.3 4.1 0.0
None - - - 15.8 20
E07 6.8 1 8.5 15.8 20
E10 10.1 1 12.7 20.3 25
E15 13.6 2 17.1 25.6 30
E20 19.5 2 24.5 34.4 35
E30 28.8 2 36.1 48.4 50
575-3-60 7.4 53.0 11.5 1.3 3.6 0.0
None - - - 13.9 20
E10 10.6 1 10.6 17.2 20
E15 15.9 1 16.0 23.6 25
E20 21.2 2 21.3 30.0 30
E30 30.4 2 30.5 41.1 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 Without Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps