Part Load Ratings - R-22 (English Units)
YCAL0041
% FULL
LOAD
DISPL.
TONS KW
Ambient
°F
UNIT
EER
100.0 35.0 38.2 95.0 9.6
75.0 28.2 24.5 83.3 11.2
50.0 20.2 14.0 69.7 14.4
25.0 10.6 6.1 55.0 17.0
IPLV: 14.0 EER
YCAL0045
% FULL
LOAD
DISPL.
TONS KW
Ambient
°F
UNIT
EER
100.0 37.8 41.8 95.0 9.6
73.2 30.3 26.0 83.0 11.5
50.0 22.1 15.5 70.0 14.5
23.2 10.8 6.2 55.0 17.0
IPLV: 14.1 EER
YCAL0051
% FULL
LOAD
DISPL.
TONS KW
Ambient
°F
UNIT
EER
100.0 43.5 48.7 95.0 9.6
69.2 33.7 28.3 81.4 11.9
48.3 24.4 17.2 68.6 14.6
20.9 13.3 7.2 55.0 18.7
IPLV: 14.4 EER
YCAL0055
% FULL
LOAD
DISPL.
TONS KW
Ambient
°F
UNIT
EER
100.0 47.6 52.8 95.0 9.6
73.5 37.2 32.3 81.9 11.4
47.0 25.0 17.2 66.5 14.6
23.5 13.0 7.8 55.0 16.3
IPLV: 13.6 EER
YCAL0061
% FULL
LOAD
DISPL.
TONS KW
Ambient
°F
UNIT
EER
100.0 55.7 62.9 95.0 9.6
69.3 42.4 35.8 80.7 11.9
46.2 30.1 20.4 67.5 15.2
23.1 15.7 9.1 55.0 17.5
IPLV: 14.3 EER
YCAL0065
% FULL
LOAD
DISPL.
TONS KW
Ambient
°F
UNIT
EER
100.0 60.0 68.3 95.0 9.6
71.5 47.4 40.3 82.4 12.1
50.0 34.7 25.3 69.6 14.5
21.5 16.2 9.0 55.0 18.2
IPLV: 14.5 EER