YORK INTERNATIONAL
48
Dimensions - YCAL0045 (SI)
VIEW B-B
100
82
171
BOTTOM OF PANEL
22 TYP.
1213
1192
1146
321
76 VICTAULIC (typ)
2292 BASE WIDTH
LEFT END
LIQUID OUT
879
401
252
ELECTRICAL ACCESS
PANEL
LIQUID IN
Aluminum Copper
YCAL
Center of Gravity (in.)
YCAL
Center of Gravity (in.)
X Y X Y
0045 1503.5 1105.5 0045 1605.9 1109.7
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
NOTE: All dimensions are in mm unless specified otherwise.