a. 56.1 Tons
b. 55.9 Compressor KW
c. 10.7 Unit EER
4. Calculate Compressor kW at 50 Tons:
5. Calculate GPM:
6. From page ____, read 6 ft of water cooler pressure
drop from GPM:
7. A YCAL0061 is suitable.
EXAMPLE - BRINE CHILLING
Example - Brine Chilling
1. Given: Provide a capacity of 34 tons cooling 30% by
weight Ethylene Glycol from 50 F to 40 F, 0.00025FF,
95 F air on the condenser, 60 Hz and 4000 ft. alti-
tude.
2. Determine:
a. Unit Size
b. KW Input
c. Ethylene Glycol GPM
d. Cooler Pressure Drop
3. See E.G. correction factors, for 30% by weight
E.G.
READ: 0.984 Tons Factor
0.997 Compr. KW factor
26.1 Gal,/ F/Tons Factor
4. See Performance Data Correction Factors for
0.00025 fouling factor and 4,000 ft. altitude.
READ: 0.975 Tons factor
1.012 kW factor
5. From RATINGS on page 16.
SELECT: YCAL0045 (English Units)
35.3 Tons
41.1 Compressor kW
6. Determine YCAL0045 brine cooling capacity and
Compressor kW requirement from pg 14:
a. TONS: = 35.3 x 0.984 x 0.975 = 33.87
b. Compr. KW = 41.1 x 0.997 x 1.012 = 41.77
7. Determine average full load Compressor kW at 34
tons
8. Determine E.G. GPM:
9. Determine Cooler Pressure Drop:
a. See E.G. correction factors for 30% by weight
E.G.
READ: 1.258 Pressure Drop factor
b. See page 14 at 88.7 GPM for YCAL0045
READ: 6.5_Water H
2
O PD
c. Cooler Pressure Drop = 6.5 x 1.258 or 8.17
A YCAL0045 is suitable.
kWkWxkW 8.499.55
1.56
50
==
GPM
FRang
e
Tons
GP
M 120
10
24
)50(
=
°
×
=
kWCompressorx
tons
tons
93
.41)77.41(
87
.33
34
=
Range
Tonfacto
rFGalTons
GP
M
min/
/.°×
=
)(7.88
10
1.260.34
GP
MGPM =
×
=