Vertical air discharge conversion kit for: SCOH-
070H (C) to 120H (C) and SCOC-076H (C) and
090H (C)
This Kit allows converting the standard horizontal air discharge,
in outdoor units SCOH/SCOC, version «V», to a vertical dis-
charge. The conversion process is as follows:
1.- Remove and discard the upper panel ref. 1 and the grid ref.
2 (fig. 1).
2.- Remove the fan, standard motor assembly on support «A»
(fig. 2).
3.- Change the motor to the proportioned and mounted sup-
port «B», making sure the pulleys are aligned (the centre
of the tensor will be at about 20 mm. from the face of the
fan) (fig. 3).
4.- Fasten the fan to the wings «C» and supports «D» of the
upper panel ref. 3, before or after mounting same on the
machine, with the new self-drilling screws included in the
Kit (fig. 3).
5.- Install the upper panel ref. 3 and the plenum cover ref. 4
(fig. 4).
6.- If the unit is to work without ducts, the protection grids
included in the kit should be mounted on the fan intakes
(self-threading screws are supplied for mounting).