SICH-070 & 076B 620 1 300 110 7
SICH-090 & 120B 620 1 520 110 8
SICH-150B 620 1 920 110 9
SICH-180B 510 2 405 165 10
Location of connecting and control
elements of internal heater accessory
SICH-070 to 180B
1 STAGE
SICH-090 to 180B
2 STAGE
Heater
model
Power supply
Power
Consumption
Stages
Automatic
switch (1)
Q1
Power
supply cable
section (2)
Front
surface
Pressure
drop (3)
V.ph.Hz kW
A
mm
2
m
2
PaA
Weight
kg
Dimensions with packing mm
Width
Depth
Height
Heater
model
Assembly and general dimensions mm
General characteristics
Notes: 1.- K curve (DIN, VDE 0660-104). 2.- Based on copper conductors. 3.- Considered the nominal air flow of the indoor section.
Dimensions with packing and weights
KM21 KM22
F21 F22
A3 A4
A3
KM12
X1
Board A3,
heater accessory
(control cable
connection)
Board A3,
heater-1
Board A4,
heater-2 accessory
(control cable
connection)
Heater power
supply cable
connection
Heater power supply
cable connecting strip
SICH-070 & 076B 400.3.50 10 15 1 20 2.5 0.53 2.9
SICH-070 & 076B 400.3.50 15 22 1 25 4 0.53 2.9
SICH-090 & 120B 400.3.50 10 15 1 20 2.5 0.74 4.9
SICH-090 & 120B 400.3.50 20 30 2 40 6 0.74 4.9
SICH-150B 400.3.50 15 22 1 25 4 0.98 7.1
SICH-150B 400.3.50 30 46 2 50 10 0.98 7.1
SICH-180B 400.3.50 15 22 1 25 4 0.98 7.1
SICH-180B 400.3.50 30 46 2 50 10 0.98 7.1