York 076-090 Technical Information Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
19
17.9 175.4 7 000 1.94 896
17.1 167.6 7 500 2.08 970
16.0 156.8 8 000 2.22 1 045
14.8 137.2 8 500 2.36 1 100
13.3 130.3 9 000 2.50 1 175
12.1 118.6 9 500 2.64 1 275
10.0 98.0 10 000 2.78 1 375
8.5 83.3 10 500 2.92 1 450
6.5 63.7 11 000 3.05 1 600
4.3 42.1 11 500 3.19 1 700
2.0 19.6 12 000 3.33 1 802
0.0 0.0 12 500 3.47 1 970
15.9 155.8 11 500 3.19 2 004
14.2 139.1 12 000 3.33 2 139
12.6 123.4 12 500 3.47 2 240
11.0 107.8 13 000 3.61 2 408
8.6 84.2 13 500 3.75 2 535
6.5 63.7 14 000 3.89 2 732
3.9 38.2 14 500 4.02 2 843
1.3 12.7 15 000 4.16 3 000
0.0 0.0 15 200 4.22 3 150
20 196 12 900 3.58 2 200
16 157 14 000 3.89 2 800
12 118 15 300 4.25 3 120
8 78 16 500 4.58 3 500
6 59 17 100 4.75 3 650
4 39 17 700 4.92 3 800
0.0 0.0 19 000 5.28 4 100
30 294.3 12 800 3.56 3 105
24 235.4 14 600 4.06 3 900
20 196 16 000 4.44 4 300
16 157 17 100 4.75 4 805
12 118 18 350 5.10 5 110
8 78 19 500 5.42 5 520
6 59 20 000 5.56 5 800
4 39 20 700 5.75 6 000
0 0 22 300 6.19 6 300
SIH-300B
SICH-150B
Absorbed
power
Model
Static pressure
available
(1)
Air flow
SICH-180B
mm WG Pa
m
3
/h m
3
/s
W
SICH-240C
Indoor fan features
(1) Values calculated with humid coil, including filters.