York 076-090 Technical Information Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
15
Flow % 80 90 100 110 120 130
Total capacity 0.960 0.980 1 1.016 1.032 1.046
Sensible capacity 0.945 0.973 1 1.038 1.075 1.118
Comp. absorb. power 0.980 0.990 1 1.009 1.017 1.025
5 3 1.5 0 -1 -2 -2.5
DB air intake
temperature
indoor unit °C
14 10 6 0 -8
23 1.20 1.04 0.96 0.77 0.58
20 1.25 1.10 1.00 0.80 0.69
17 1.30 1.13 1.04 0.83 0.63
WB air temperature
outdoor unit °C
-2 -1.5 -0.5 0 0.5 1 1.2
SCOH-070H (C) SICH-070/076B 20 000 8 000 17 300 7 300 62
SCOH-0706H (C) SICH-070/076B 22 500 9 500 22 300 7 700 62
SCOH-090H (C) SICH-090/120B 30 000 11 000 33 500 12 700 75
SCOH-120H (C) SICH-090/120B 32 000 13 700 37 000 15 200 75
SCOH-150H (C) SICH-150B 44 000 16 500 44 000 16 200 75
SCOH-180H (C) SICH-180B 49 000 24 400 51 000 21 000 80
SCOH-240H (C) SICH-240C 74 000 30 800 74 000 26 000 80
SCOH-300H (C) SIH-300B 86 000 36 800 88 000 34 000 80
Outdoor unit
Indoor unit
WinterSummer
Available pressure
indoor fan
Pa
Consumption W
Heating
capacity W
Cooling
capacity W
Consumption W
Nominal characteristics
Correcting factors
Correcting factors for the cooling capacities
Cooling capacity correcting factors for flows that vary from
the nominal flows in the indoor coil.
Correction of the real temperature of the air intake to the
outdoor coil for flows that vary from the nominal flows.
Correcting factors for heating capacities
Correction of the real temperature of the air intake to the out-
door coil for flows that vary from the nominal flows.
Correction in °C on real
temperature of air intake
to the outdoor coil
Flow % 70 80 90 100 110 120 130
Flow % 70 80 90 100 110 120 130
Correction in °C on real
temperature of air intake
to the outdoor coil