Discharge temperature surpassed or probe short
circuited
1
2
High pressure switch, outdoor fan thermal switch or com-
pressor module thermal switch
3
Low pressure switch
4
Indoor fan thermal switch
5
Repeated star-ups in cool or suction temperature <-25ºC
6 Low liquid temperature <-30ºC
Flashes Meaning
detected and not reset is indicated.
The following table shows the possible failures:
Reset
The incidents, with a few exceptions, do not need to be reset.
They reset automatically once the cause has disappeared.
The following incidents require resetting, and are reset in the
same way as the alarms:
a) Accessory disappeared.
b) Repeated defrost cycles (also reset if a defrost cycle ends
under normal conditions)
c) Electric heating thermal switch.
The alarms can be reset as follows:
1) Setting the thermostat to OFF, if communication with the
thermostat has been implemented.
2) Pressing the reset button on the electronic board.
3) Disconnecting and reconnecting power supply to the elec-
tronic board.
4) By means of the communications trunk.
It is worth pointing out that, with a reset by means of setting
the thermostat to OFF, the board cannot be reset more than 3
times a day.