Page view 42
528194-YTG-F-1210
Johnson Controls Unitary Products 43
120
(10)
208 13.9 110 21.7 3.5 9.6 5.5 10
None - - - 57.9 63.4 70 70
E18 13.5 2 37.5 71.3 78.2 80 80
E24 18 2 50.0 87 93.8 90 100
E36 25.5 2 70.8 113 119.9 125 125
E54 40.6 2 112.7 165.4 172.2 175 175
230 13.9 110 21.7 3.5 9.6 5.5 10
None - - - 57.9 63.4 70 70
E18 18 2 43.3 78.6 85.5 80 90
E24 24 2 57.7 96.7 103.5 100 110
E36 34 2 81.8 126.7 133.6 150 150
E54 54 2 129.9 154.4 161.3 175 175
460 7.4 55 11.5 1.6 4.8 2.2 5
None - - - 29.7 31.9 35 35
E18 18 2 21.7 39.3 42.1 40 45
E24 24 2 28.9 48.3 51.1 50 60
E36 34 2 40.9 63.4 66.1 70 70
E54 54 2 65.0 77.2 80 90 90
575 5.6 43 8.7 1.3 3.9 1.8 4
None - - - 23.1 24.9 25 30
E18 18 2 17.3 31.5 33.8 35 35
E24 24 2 23.1 38.7 41 40 45
E36 34 2 32.7 50.8 53 60 60
E54 54 2 52.0 61.8 64.1 70 70
150
(12.5)
208 23.1 160 36 3.5 15.2 5.5 10
None - - - 91.2 96.7 110 110
E18 13.5 2 37.5 91.2 96.7 110 110
E24 18 2 50.0 94.0 100.8 110 110
E36 25.5 2 70.8 120.0 126.9 125 150
E54 40.6 2 112.7 172.4 179.2 175 200
230 23.1 160 36 3.5 15.2 5.5 10
None - - - 91.2 96.7 110 110
E18 18 2 43.3 91.2 96.7 110 110
E24 24 2 57.7 103.7 110.5 110 125
E36 34 2 81.8 133.7 140.6 150 150
E54 54 2 129.9 161.4 168.3 175 175
460 12.2 87 19 1.6 7.6 2.2 5
None - - - 46.5 48.7 50 60
E18 18 2 21.7 46.5 48.7 50 60
E24 24 2 28.9 51.8 54.6 60 60
E36 34 2 40.9 66.9 69.6 70 70
E54 54 2 65.0 80.7 83.5 90 90
575 8.7 62 13.5 1.3 6.1 1.8 4
None - - - 34.9 36.7 40 45
E18 18 2 17.3 34.9 36.7 40 45
E24 24 2 23.1 41.5 43.7 45 45
E36 34 2 32.7 53.5 55.8 60 60
E54 54 2 52.0 64.6 66.8 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps