York R-410A User Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
528194-YTG-F-1210
18 Johnson Controls Unitary Products
115°F 125°F
1625
77 75.2 7.3 29.2 26.1 18.9 - - - 68.0 7.9 28.3 22.9 16.6 - - -
72 67.9 7.1 43.8 36.6 29.3 22.1 - - 60.9 7.7 41.0 33.9 26.8 19.6 - -
67 60.5 7.0 58.4 47.1 39.8 32.6 25.4 - 53.8 7.5 53.8 44.1 36.9 29.8 22.7 -
62 56.1 6.8 56.1 56.1 47.7 40.5 33.3 26.0 50.9 7.3 50.9 50.9 43.7 36.6 29.4 22.3
1950
77 77.6 7.3 37.8 29.4 20.9 - - - 70.1 7.9 37.5 26.8 18.5 - - -
72 70.0 7.2 49.4 41.0 32.6 24.2 - - 62.7 7.7 46.5 38.1 29.8 21.5 - -
67 62.4 7.0 61.0 52.6 44.2 35.8 27.4 - 55.4 7.5 55.4 49.5 41.2 32.9 24.5 -
62 57.8 6.9 57.8 57.8 52.9 44.5 36.1 27.7 52.4 7.4 52.4 52.4 48.7 40.4 32.1 23.8
57 53.2 6.8 53.2 53.2 46.1 37.7 29.2 20.8 45.1 7.2 45.1 45.1 38.3 29.9 21.6 13.3
2275
77 80.0 7.4 46.3 32.6 23.0 - - - 72.1 8.0 46.8 30.8 20.4 - - -
72 72.2 7.2 55.0 45.4 35.8 26.2 - - 64.6 7.8 51.9 42.4 32.9 23.4 - -
67 64.3 7.0 63.6 58.2 48.6 39.0 29.4 - 57.0 7.6 57.0 54.9 45.4 35.9 26.4 -
62 59.6 6.9 59.6 59.6 58.2 48.6 39.0 29.4 53.9 7.4 53.9 53.9 53.8 44.3 34.8 25.3
57 54.8 6.8 54.8 54.8 50.6 41.0 31.4 21.8 46.4 7.2 46.4 46.4 42.2 32.7 23.2 13.7
2600
77 82.3 7.4 54.9 35.9 25.1 - - - 74.2 8.0 56.0 34.7 22.3 - - -
72 74.3 7.2 60.6 49.8 39.0 28.2 - - 66.4 7.8 57.3 46.7 36.0 25.3 - -
67 66.2 7.1 66.2 63.7 52.9 42.1 31.4 - 58.6 7.6 58.6 58.6 49.7 39.0 28.3 -
62 61.4 7.0 61.4 61.4 63.4 52.6 41.9 31.1 55.5 7.5 55.5 55.5 55.5 48.1 37.4 26.8
57 56.5 6.9 56.5 56.5 55.2 44.4 33.6 22.8 47.7 7.3 47.7 47.7 46.2 35.6 24.9 14.2
2925
72 75.5 7.3 65.8 53.9 42.0 30.1 - - 67.4 7.8 62.5 50.7 38.9 27.0 - -
67 67.3 7.1 67.3 66.1 57.0 45.1 33.2 - 59.5 7.6 59.5 59.5 53.6 41.8 30.0 -
62 62.4 7.0 62.4 62.4 63.4 51.5 39.7 27.8 56.3 7.5 56.3 56.3 56.3 46.2 34.4 22.6
57 57.4 6.9 57.4 57.4 56.8 44.9 33.0 21.1 48.4 7.3 48.4 48.4 47.7 35.9 24.1 12.3
3250
72 76.8 7.3 71.0 58.0 45.0 32.0 - - 68.5 7.9 67.6 54.7 41.7 28.8 - -
67 68.4 7.1 68.4 68.4 61.1 48.1 35.1 - 60.5 7.7 60.5 60.5 57.6 44.6 31.7 -
62 63.4 7.0 63.4 63.4 63.4 50.4 37.5 24.5 57.2 7.5 57.2 57.2 57.2 44.3 31.3 18.4
57 58.4 6.9 58.4 58.4 58.4 45.4 32.4 19.4 49.1 7.4 49.1 49.1 49.1 36.2 23.3 10.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65