528194-YTG-F-1210
26 Johnson Controls Unitary Products
115°F 125°F
3125
77 152.8 14.9 60.7 48.8 36.4 - - - 140.3 16.2 52.4 44.0 31.5 - - -
72 139.4 14.8 83.7 71.3 58.8 46.3 - - 127.6 16.2 79.0 66.6 54.2 41.7 - -
67 125.9 14.7 106.7 93.7 81.2 68.8 56.3 - 114.9 16.1 102.4 89.2 76.8 64.4 51.9 -
62 117.0 14.5 117.0 117.0 100.3 87.8 75.4 62.9 108.6 15.9 108.6 108.6 94.4 82.0 69.6 57.2
3750
77 158.0 14.9 68.1 54.0 40.0 - - - 145.1 16.3 62.7 48.8 34.9 - - -
72 144.1 14.8 92.7 78.7 64.6 50.6 - - 132.0 16.2 87.7 73.8 59.8 45.9 - -
67 130.1 14.7 117.4 103.3 89.3 75.2 61.2 - 118.9 16.1 112.6 98.7 84.8 70.8 56.9 -
62 121.0 14.5 121.0 121.0 110.2 96.2 82.1 68.1 112.4 15.9 112.4 112.4 104.3 90.3 76.4 62.5
57 119.1 14.6 119.1 119.1 110.7 96.6 82.6 68.5 110.5 16.0 110.5 110.5 102.6 88.6 74.7 60.8
4375
77 163.2 14.9 75.4 59.2 43.6 - - - 150.0 16.3 73.0 53.7 38.2 - - -
72 148.8 14.8 101.7 86.1 70.5 54.8 - - 136.4 16.2 96.4 80.9 65.5 50.0 - -
67 134.4 14.7 128.0 113.0 97.3 81.7 66.1 - 122.9 16.1 122.8 108.2 92.8 77.3 61.9 -
62 125.0 14.6 125.0 125.0 120.1 104.5 88.9 73.3 116.1 15.9 116.1 116.1 114.1 98.7 83.2 67.8
57 123.0 14.6 123.0 123.0 120.6 105.0 89.4 73.8 114.2 16.0 114.2 114.2 112.3 96.8 81.4 66.0
5000
77 168.3 15.0 82.8 64.4 47.2 - - - 154.8 16.3 83.3 58.5 41.5 - - -
72 153.5 14.9 110.7 93.5 76.3 59.1 - - 140.8 16.3 105.1 88.1 71.2 54.2 - -
67 138.7 14.8 138.7 122.6 105.4 88.2 71.0 - 126.8 16.2 126.8 117.7 100.8 83.8 66.8 -
62 128.9 14.6 128.9 128.9 130.1 112.9 95.7 78.4 119.9 16.0 119.9 119.9 119.9 107.0 90.0 73.1
57 126.9 14.6 126.9 126.9 130.6 113.4 96.2 79.0 117.9 16.0 117.9 117.9 117.9 105.0 88.1 71.1
5625
72 156.2 14.9 118.3 99.9 81.4 63.0 - - 143.0 16.2 112.2 94.1 75.9 57.8 - -
67 141.1 14.8 141.1 130.9 112.5 94.1 75.6 - 128.7 16.2 128.7 125.7 107.6 89.4 71.3 -
62 131.2 14.6 131.2 131.2 131.8 113.3 94.9 76.5 121.7 16.0 121.7 121.7 121.7 105.6 87.5 69.3
57 129.2 14.6 129.2 129.2 131.0 112.6 94.2 75.7 119.6 16.0 119.6 119.6 119.6 103.6 85.4 67.3
6250
72 158.9 14.9 125.8 106.2 86.6 66.9 - - 145.1 16.2 119.4 100.0 80.7 61.4 - -
67 143.6 14.8 143.6 139.2 119.6 99.9 80.3 - 130.6 16.2 130.6 130.6 114.3 95.0 75.7 -
62 133.5 14.6 133.5 133.5 133.5 113.8 94.2 74.6 123.5 16.0 123.5 123.5 123.5 104.2 84.9 65.6
57 131.4 14.6 131.4 131.4 131.4 111.8 92.1 72.5 121.4 16.0 121.4 121.4 121.4 102.1 82.8 63.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF150 (12.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
Page view 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 67 68