Johnson Controls Unitary Products 29
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YZB04211
INDOOR COIL MODEL NO. FC/MC/PC/UC48
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 57 57 62 62 67 72
65
T.C. 41.7 43.4 41.3 47.3 50.7 44.2 44.8 42.6 48.5 50.4 46.8 46.3 44.0 49.8 50.1
S.C. 38.3 36.4 31.1 30.9 24.9 40.5 40.1 33.1 33.6 26.0 42.8 43.8 35.0 36.3 27.0
K.W. 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
75
T.C. 40.0 41.2 39.4 44.8 47.5 42.3 42.8 40.5 46.0 47.5 44.7 44.4 41.7 47.2 47.4
S.C. 36.7 35.5 29.9 29.9 23.4 38.8 38.5 31.9 32.5 24.6 40.8 41.6 34.0 35.0 25.9
K.W. 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 3.0
85
T.C. 38.3 39.1 37.5 42.4 44.4 40.4 40.8 38.4 43.5 44.6 42.5 42.6 39.3 44.6 44.8
S.C. 35.2 34.5 28.6 29.0 21.9 37.0 37.0 30.8 31.4 23.3 38.8 39.5 33.0 33.8 24.7
K.W. 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
95
T.C. 36.7 36.9 35.6 40.0 41.3 38.5 38.9 36.3 41.0 41.7 40.4 40.8 37.0 42.0 42.1
S.C. 33.6 33.5 27.3 28.0 20.4 35.2 35.4 29.7 30.3 21.9 36.8 37.3 32.0 32.6 23.5
K.W. 3.6 3.6 3.6 3.6 3.7 3.7 3.6 3.6 3.6 3.7 3.7 3.6 3.6 3.6 3.7
105
T.C. 35.5 34.9 33.2 37.5 38.9 36.3 36.6 33.8 38.4 39.3 37.1 38.4 34.5 39.3 39.7
S.C. 32.5 31.7 26.3 27.1 19.9 33.2 33.4 28.3 29.4 21.5 33.9 35.1 30.4 31.6 23.0
K.W. 4.2 4.1 4.1 4.1 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
115
T.C. 34.4 33.0 30.9 35.0 36.5 34.2 34.5 31.4 35.8 36.9 34.0 36.0 32.0 36.7 37.3
S.C. 31.5 30.0 25.2 26.2 19.4 31.2 31.5 27.0 28.4 21.0 31.0 33.0 28.8 30.7 22.6
K.W. 4.7 4.6 4.6 4.6 4.7 4.6 4.6 4.6 4.7 4.7 4.6 4.7 4.6 4.7 4.7
125
T.C. 33.3 31.0 28.6 32.6 34.1 32.1 32.3 29.1 33.3 34.5 30.8 33.6 29.5 34.0 34.9
S.C. 30.4 28.3 24.2 25.2 19.0 29.3 29.5 25.8 27.5 20.5 28.1 30.8 27.3 29.8 22.1
K.W. 5.1 5.1 5.1 5.1 5.2 5.1 5.1 5.1 5.1 5.2 5.1 5.2 5.1 5.2 5.2
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
MA16C FC/MC48C 1.00 1.00 1.00
MA14D FC/MC48D 1.00 1.00 1.00
MA16C FC60C 1.00 1.00 1.00
MV16C FC/MC48C 1.02 1.02 0.96
MV20D FC/MC48D 1.02 1.02 0.96
AHP/SHP48 1.00 1.00 1.00
AV/SV48 1.01 1.02 0.96
HC42 0.98 0.96 1.00
HD48 0.98 0.98 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*C16 FC/MC/PC48C 1.00 0.90 1.01
PV8*C20 FC/MC/PC48C 1.00 0.90 1.03
P(C,V)9*C16 FC/MC/PC48C 1.00 0.90 1.03
P(C,V)9*C20 FC/MC/PC48C 1.00 0.90 1.01
P(C,V)9*D20 FC/MC/PC48D 1.00 0.90 1.03
Y*(8,L)C*C16 FC/MC/PC48C 1.02 1.03 0.96
Y*(8,L)C*C20 FC/MC/PC48C 1.02 1.03 0.96
Y*9C*C16 FC/MC/PC48C 1.01 1.03 0.97
Y*9C*C20 FC/MC/PC48C 1.01 1.02 0.98
Y*9C*D20 FC/MC/PC48D 1.02 1.03 0.97
Y*(8,L)C*B12 HD48 0.99 0.97 0.98
Y*(8,L)C*C16 HD48 1.02 1.02 0.96
Y*(8,L)C*C20 HD48 1.02 1.02 0.95
Y*9C*B12 HD48 0.97 0.91 0.95
Y*9C*C16 HD48 0.99 0.99 0.97
Y*9C*C20 HD48 0.99 0.99 0.97
Y*9C*D20 HD48 1.02 1.02 0.97
Y*(8,L)C*C16 UC48C 1.01 1.03 0.96
Y*(8,L)C*C20 UC48C 1.01 1.03 0.96
Y*9C*C16 UC48C 1.00 1.02 0.97
Y*9C*C20 UC48C 1.00 1.02 0.98
Y*9C*D20 UC48D 1.00 1.02 0.97
G*9V*C16 FC/MC/PC48C 1.01 1.03 0.97
G*9V*C20 FC/MC/PC48C 1.01 1.02 0.98
G*9V*D20 FC/MC/PC48D 1.02 1.03 0.97
G*9V*B12 HD48 0.97 0.91 0.95
G*9V*C16 HD48 0.99 0.99 0.97
G*9V*C20 HD48 0.99 0.99 0.97
G*9V*D20 HD48 1.02 1.02 0.97
G*9V*C16 UC48C 1.00 1.02 0.97
G*9V*C20 UC48C 1.00 1.02 0.98
G*9V*D20 UC48D 1.00 1.02 0.97
Variable Speed