FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
TECHNICAL GUIDE
MILLENNIUM
®
SINGLE PACKAGE ROOFTOP UNITS
Y
32, Y33 & Y34
25, 30, & 40 TON
25 TON (10 EER)
30 & 40 TON (9.5 EER)
®
30 TON UNIT SHOWN
ISO 9001
Certified Quality
Management System
TOMORROW’S UNIT TODAY
GENERAL
Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. Millennium units are manu-
factured at an ISO 9001 registered facility, and each rooftop
is completely computer-run tested prior to shipment.
The Millennium is designed to be flexible enough to meet
your needs today and in the future. The true value of YORK’s
Millennium is that it can be designed to fit any need, from
cooling only, constant volume applications to variable air vol-
ume systems with variable frequency drive.
FEATURING:
Cooling Only Units
Cooling/Gas Heating Units (Natural) Standard or
Modulating Gas Heat available
Cooling/Electric Heating Units
Cooling/Hot Water Heating Units
Cooling/Steam Heating Units
Industry Leading Efficiency
Double Wall Construction
Stainless Steel or Powder Coated Drain Pan
Multiple Scroll Compressors
Multiple Refrigeration Circuits
Upgradable Motor Efficiency
Enhanced Filtration
Vibration Isolated Supply Fan and Motor
Technicoated Evaporator and Condenser Coils
High Capacity Evaporator Coils
Single Power Point Connection
Easy Access Hinged Doors
Variable Air Volume
Constant Air Volume
Factory Installed Economizers/Disconnect/Convenience
Outlet/Control Options
•Low Profile
MILLENNIUM SIMPLICITY
®
ELITE™ FEATURES:
Single Button Programming and LED Display
Designed to operate on both constant and variable air
volume units
365-Day real time clock with automatic Daylight Savings
time adjustment
Occupancy Schedule allowing two schedules per day
20 Holiday schedules with programmable schedules that
can start at any time, day or night
Patented Comfort Ventilation operation for economical
and comfortable economizer operation
Demand Ventilation option to assure proper IAQ condi-
tions based on available space or return air CO
2
levels
Temperature/Humidity programming algorithm allows
programmable limits to help control humidity in the space
Smoke Purge automatically ventilates the space when
smoke is detected
Monitors dirty filters and proves airflow before starting
heating or cooling
Intelligent recovery to bring the space temperature up to
occupied setting quicker and more economically
Page view 0
1 2 3 4 5 6 ... 95 96

Summary of Contents

Page 1 - TECHNICAL GUIDE

246653-YTG-E-0108FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALETECHNICAL GUIDE MILLENNIUM®SINGLE PACKAGE ROOFTOP UNITSY32, Y33 &am

Page 2 - TABLE OF CONTENTS

246653-YTG-E-010810 Johnson Controls Unitary Products* Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2/1.TABLE 1: GENE

Page 3 - LIST OF FIGURES

246653-YTG-E-0108Johnson Controls Unitary Products 11SELECTION PROCEDUREGIVEN:Required Cooling Capacity 460,000 BtuhRequired Sensible Cooling 390,000

Page 4 - LIST OF TABLES

246653-YTG-E-010812 Johnson Controls Unitary ProductsTABLE 3: STANDARD GAS HEATING CAPACITIESGAS HEAT OPTIONAVAILABLE ON MODELSINPUT CAPACITY (MBH)11.

Page 5 - FEATURES AND BENEFITS

246653-YTG-E-0108Johnson Controls Unitary Products 13TABLE 7: MODULATING HEATSTAGES OF GAS CONTROL (% OF FULL HEAT OUTPUT)GAS HEAT OPTION AVAILABLE ON

Page 6 - INSTALLATION FEATURES

246653-YTG-E-010814 Johnson Controls Unitary ProductsHOT WATER HEATING1The YORK Millennium Rooftop units (30 - 40 Ton sizes) canbe furnished with a YO

Page 7 - CONSTRUCTION FEATURES

246653-YTG-E-0108Johnson Controls Unitary Products 15FIGURE 1 - HOT WATER PIPING CROSS-SEC-TIONTABLE 12: STATIC RESISTANCE HOT WATER COIL (1 ROW, 40

Page 8 - LIST OF FEATURES AND BENEFITS

246653-YTG-E-010816 Johnson Controls Unitary ProductsFIGURE 2 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 10 GPMFIGURE 3 - HOT WATER COIL - 25 &am

Page 9 - NOMENCLATURE

246653-YTG-E-0108Johnson Controls Unitary Products 17FIGURE 4 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 30 GPMFIGURE 5 - HOT WATER COIL - 25 &am

Page 10 - 246653-YTG-E-0108

246653-YTG-E-010818 Johnson Controls Unitary ProductsFIGURE 6 - HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPMFIGURE 7 - HOT WATER COIL - 40 TON, 1 ROW,

Page 11 - SELECTION PROCEDURE

246653-YTG-E-0108Johnson Controls Unitary Products 19FIGURE 8 - HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPMFIGURE 9 - HOT WATER COIL - 40 TON, 1 ROW,

Page 12 - TABLE 5: MINIMUM HEATING CFM

246653-YTG-E-01082 Johnson Controls Unitary ProductsTABLE OF CONTENTSGENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 13 - TABLE 7: MODULATING HEAT

246653-YTG-E-010820 Johnson Controls Unitary ProductsPHYSICAL DATA HOT WATER COIL - 2 ROWCoil Casing . . . . . . . . . . . . . . . . . . . . Galvanize

Page 14 - HOT WATER HEATING

246653-YTG-E-0108Johnson Controls Unitary Products 21FIGURE 10 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 20 GPMFIGURE 11 - HOT WATER COIL - 25 &

Page 15 - (1 ROW, 40 TON)

246653-YTG-E-010822 Johnson Controls Unitary ProductsFIGURE 12 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 60 GPMFIGURE 13 - HOT WATER COIL - 25 &

Page 16

246653-YTG-E-0108Johnson Controls Unitary Products 23FIGURE 14 - HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPMFIGURE 15 - HOT WATER COIL - 40 TON, 2 ROW

Page 17

246653-YTG-E-010824 Johnson Controls Unitary ProductsFIGURE 16 - HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPMFIGURE 17 - HOT WATER COIL - 40 TON, 2 ROW

Page 18

246653-YTG-E-0108Johnson Controls Unitary Products 25STEAM HEATINGThe YORK Millennium units (25, 30, and 40 ton sizes) can bemanufactured with a steam

Page 19

246653-YTG-E-010826 Johnson Controls Unitary ProductsFIGURE 19 - STEAM COIL - 25 & 30 TON, 1 ROWFIGURE 20 - STEAM COIL - 40 TON, 1 ROW1801902002

Page 20

246653-YTG-E-0108Johnson Controls Unitary Products 27TABLE 24: EXHAUST FAN DRIVE DATAMODELBLOWER RPM RANGEMOTOR MOTOR PULLEY BLOWER PULLEY BELTSHPFR

Page 21

246653-YTG-E-010828 Johnson Controls Unitary ProductsSUPPLY AIR DRIVE ADJUSTMENTAt unit start-up, the measured CFM may be higher or lowerthan the spec

Page 22

246653-YTG-E-0108Johnson Controls Unitary Products 29NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.2) Class I Blowers a

Page 23

246653-YTG-E-0108Johnson Controls Unitary Products 3LIST OF FIGURESFig.# Pg.#1 HOT WATER PIPING CROSS-SECTION . . . . . . . .

Page 24

246653-YTG-E-010830 Johnson Controls Unitary ProductsTABLE 29: DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON5 HP MOTOR & 759 RPM DRIVE 7.5 HP MOTOR

Page 25 - B A S E R A I L

246653-YTG-E-0108Johnson Controls Unitary Products 31TABLE 31: COOLING PERFORMANCE 25 TONAIR ON EVAPORATOR COILTEMPERATURE OF AIR ON CONDENSER COIL75°

Page 26

246653-YTG-E-010832 Johnson Controls Unitary ProductsTABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COILAIR ON EVAPORATOR COILTEMPERATURE OF A

Page 27

246653-YTG-E-0108Johnson Controls Unitary Products 33TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMP

Page 28 - SUPPLY AIR DRIVE ADJUSTMENT

246653-YTG-E-010834 Johnson Controls Unitary ProductsTABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMP

Page 29

246653-YTG-E-0108Johnson Controls Unitary Products 35TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COILAIR ON EVAPORATOR COILTEMPERATURE OF AIR O

Page 30

246653-YTG-E-010836 Johnson Controls Unitary ProductsTABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMPERAT

Page 31

246653-YTG-E-0108Johnson Controls Unitary Products 37TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMPERAT

Page 32

246653-YTG-E-010838 Johnson Controls Unitary ProductsTABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COILAIR ON EVAPORATOR COILTEMPERATURE OF A

Page 33

246653-YTG-E-0108Johnson Controls Unitary Products 39TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMP

Page 34

246653-YTG-E-01084 Johnson Controls Unitary ProductsLIST OF TABLESTbl.# Pg.#1 GENERAL PHYSICAL DATA . . . . . . . . . . . . .

Page 35

246653-YTG-E-010840 Johnson Controls Unitary ProductsTABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMP

Page 36

246653-YTG-E-0108Johnson Controls Unitary Products 41TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COILAIR ON EVAPORATOR COILTEMPERATURE OF AIR O

Page 37

246653-YTG-E-010842 Johnson Controls Unitary ProductsTABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMPERAT

Page 38

246653-YTG-E-0108Johnson Controls Unitary Products 43TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL (CONTINUED)AIR ON EVAPORATOR COILTEMPERAT

Page 39

246653-YTG-E-010844 Johnson Controls Unitary ProductsCFM, STATIC PRESSURE, AND POWER - ALTI-TUDE AND TEMPERATURE CORRECTIONSThe information below shou

Page 40

246653-YTG-E-0108Johnson Controls Unitary Products 45FIGURE 21 - ALTITUDE/TEMPERATURE CONVERSION FACTOR

Page 41

246653-YTG-E-010846 Johnson Controls Unitary Products4. Shaded RPMs require Class II blower.TABLE 37: FAN PERFORMANCE - 25 TON1, 2AIRFLOW CFMAVAILABLE

Page 42

246653-YTG-E-0108Johnson Controls Unitary Products 47FIGURE 22 - FAN PERFORMANCE - 25 TON0 1 2 3 4 5 6 7 8 9 10 11 12 13CFM (x1000)0.00.51.01.52.02.5

Page 43

246653-YTG-E-010848 Johnson Controls Unitary Products4. Shaded RPMs require Class II blower.TABLE 38: FAN PERFORMANCE - 30 TON 1, 2AIRFLOW (CFM)AVAILA

Page 44

246653-YTG-E-0108Johnson Controls Unitary Products 49FIGURE 23 - FAN PERFORMANCE - 30 TON0 2 4 6 8 10 12 14 16 18 20CFM (x1000)0.00.51.01.52.02.53.03

Page 45

246653-YTG-E-0108Johnson Controls Unitary Products 5YORK Millennium®OVERVIEW Introducing the YORK Millennium 25, 30, & 40 ton rooftopline - units

Page 46

246653-YTG-E-010850 Johnson Controls Unitary Products4. Shaded RPMs require Class II blower.TABLE 39: FAN PERFORMANCE - 40 TON1,2AIRFLOW (CFM)AVAILABL

Page 47 - 25 Ton Forward Curve

246653-YTG-E-0108Johnson Controls Unitary Products 51FIGURE 24 - FAN PERFORMANCE - 40 TON40 Ton Forward CurveA - Standard UnitNote: Standard Unit in

Page 48

246653-YTG-E-010852 Johnson Controls Unitary ProductsTABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL1,2AIRFLOW (CFM)AVAILABLE EXTERNAL STATIC PRES

Page 49 - 30 Ton Forward Curve

246653-YTG-E-0108Johnson Controls Unitary Products 534. Shaded RPMs require Class II blower.AIRFLOW (CFM)AVAILABLE EXTERNAL STATIC PRESSURE (IWG)4.2 4

Page 50

246653-YTG-E-010854 Johnson Controls Unitary ProductsTABLE 41: FAN PERFORMANCE - 40 TON AIRFOIL1,2AIRFLOW (CFM)AVAILABLE EXTERNAL STATIC PRESSURE (IWG

Page 51 - 40 Ton Forward Curve

246653-YTG-E-0108Johnson Controls Unitary Products 554. Shaded RPMs require Class II blower.AIRFLOW (CFM)AVAILABLE EXTERNAL STATIC PRESSURE (IWG)3.2 3

Page 52

246653-YTG-E-010856 Johnson Controls Unitary ProductsTABLE 42: COMPONENT STATIC RESISTANCE1, 2COMPONENT COIL LOSSESCFM6,000 8,000 10,000 12,000 14,000

Page 53 - (CONTINUED)

246653-YTG-E-0108Johnson Controls Unitary Products 57TABLE 43: POWER EXHAUST - ONE FORWARD CURVED FAN 25 TON1AIRFLOW CFMAVAILABLE EXTERNAL STATIC PRES

Page 54

246653-YTG-E-010858 Johnson Controls Unitary ProductsFIGURE 25 - POWER EXHAUST - ONE FORWARD CURVE FAN - 25 TONSPower Exhaust 25 Ton0.00.51.01.52.02.

Page 55

246653-YTG-E-0108Johnson Controls Unitary Products 59TABLE 44: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON1AIRFLOW CFMAVAILABLE EXTERNAL

Page 56

246653-YTG-E-01086 Johnson Controls Unitary ProductsOptional Head Pressure Control - For those applicationswhere mechanical cooling is required below

Page 57

246653-YTG-E-010860 Johnson Controls Unitary ProductsFIGURE 26 - POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TONS

Page 58 - Power Exhaust 25 Ton

246653-YTG-E-0108Johnson Controls Unitary Products 61TABLE 45: ELECTRICAL DATA 25 TON BASIC UNIT R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY

Page 59

246653-YTG-E-010862 Johnson Controls Unitary ProductsTABLE 47: ELECTRICAL DATA 40 TON BASIC UNIT R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY

Page 60

246653-YTG-E-0108Johnson Controls Unitary Products 63TABLE 48: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH

Page 61

246653-YTG-E-010864 Johnson Controls Unitary ProductsTABLE 49: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH

Page 62

246653-YTG-E-0108Johnson Controls Unitary Products 65TABLE 50: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH

Page 63

246653-YTG-E-010866 Johnson Controls Unitary ProductsTABLE 51: ELECTRICAL DATA 25 TON WITH POWER EXHAUST R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH

Page 64

246653-YTG-E-0108Johnson Controls Unitary Products 67TABLE 52: ELECTRICAL DATA 30 TON WITH POWER EXHAUST R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH

Page 65

246653-YTG-E-010868 Johnson Controls Unitary ProductsTABLE 53: ELECTRICAL DATA 40 TON WITH POWER EXHAUST R22VOLTAGECOMPRESSORS(EACH)OD FAN MOTORS(EACH

Page 66

246653-YTG-E-0108Johnson Controls Unitary Products 69TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 VOLTAGEELECTRIC HEATCOM

Page 67

246653-YTG-E-0108Johnson Controls Unitary Products 7CONSTRUCTION FEATURESYORK's Millennium rooftop line is built for the long haul, withhigh end

Page 68

246653-YTG-E-010870 Johnson Controls Unitary ProductsVOLTAGEELECTRIC HEATCOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY BLOWER PWR EXH MOTORMCA1(AMPS)MAXF

Page 69

246653-YTG-E-0108Johnson Controls Unitary Products 71VOLTAGEELECTRIC HEATCOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY BLOWER PWR EXH MOTORMCA1(AMPS)MAXF

Page 70

246653-YTG-E-010872 Johnson Controls Unitary ProductsTABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 VOLTAGEELECTRIC HEATCOM

Page 71

246653-YTG-E-0108Johnson Controls Unitary Products 73VOLTAGEELECTRIC HEATCOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY BLOWER PWR EXH MOTORMCA1(AMPS)MAXF

Page 72

246653-YTG-E-010874 Johnson Controls Unitary ProductsVOLTAGEELECTRIC HEATCOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY BLOWER PWR EXH MOTORMCA1(AMPS)MAXF

Page 73

246653-YTG-E-0108Johnson Controls Unitary Products 75TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 VOLTAGEELECTRIC HEATCOM

Page 74

246653-YTG-E-010876 Johnson Controls Unitary ProductsVOLTAGEELECTRIC HEATCOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY BLOWER PWR EXH MOTORMCA1(AMPS)MAXF

Page 75

246653-YTG-E-0108Johnson Controls Unitary Products 77VOLTAGEELECTRIC HEATCOMPRESSORS(EACH)OD FAN MOTORS(EACH)SUPPLY BLOWER PWR EXH MOTORMCA1(AMPS)MAXF

Page 76

246653-YTG-E-010878 Johnson Controls Unitary ProductsNOTE: If the Millennium is VAV with ERV, add the weight of an exhaust VFD - it will be in the uni

Page 77

246653-YTG-E-0108Johnson Controls Unitary Products 79NOTES:Basic Unit = cooling only, 10hp FC fan.+ Econ = +235lb+ Heat = single stage gas, 180 lb+ Po

Page 78 - TABLE 57: UNIT WEIGHTS

246653-YTG-E-01088 Johnson Controls Unitary ProductsLIST OF FEATURES AND BENEFITSStandard Features• 9.5 EER (10 EER on 25 ton)• Double wall constructi

Page 79 - TABLE 63: ATTENUATION FACTORS

246653-YTG-E-010880 Johnson Controls Unitary ProductsFIGURE 28 - COMPONENT LOCATIONFILTER ACCESSEVAPORATOR COILAND DRAINPAN ACCESSPOWER & CONTROL

Page 80

246653-YTG-E-0108Johnson Controls Unitary Products 81FIGURE 29 - END RETURN, BOTTOM SUPPLYRETURN AIR SUPPLY AIR 240"64"92"80.93"S

Page 81

246653-YTG-E-010882 Johnson Controls Unitary ProductsFIGURE 30 - BOTTOM SUPPLY AND RETURN88.7"CLCL240"38.59"83"4.5"4.5"

Page 82

246653-YTG-E-0108Johnson Controls Unitary Products 83FIGURE 31 - BOTTOM RETURN, FRONT & REAR SUPPLYFRONT SUPPLY: FOR COOLING ONLY APPLICATIONSRE

Page 83

246653-YTG-E-010884 Johnson Controls Unitary ProductsFIGURE 32 - END RETURN, FRONT & REAR SUPPLYFRONT SUPPLY: FOR COOLING ONLY APPLICATIONS REAR

Page 84

246653-YTG-E-0108Johnson Controls Unitary Products 85FIGURE 33 - MILLENNIUM OVERHEAD VIEW259.6835.4239.3193.43241.22FIGURE 34 - MILLENNIUM MAJOR COM

Page 85

246653-YTG-E-010886 Johnson Controls Unitary ProductsFIGURE 35 - MILLENNIUM CABINET DOOR CONFIGURATIONBACK VIEW123 4Hinged,Tool-FreeDoorOptionalHinge

Page 86

246653-YTG-E-0108Johnson Controls Unitary Products 87FIGURE 36 - CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - SIDEFIGURE 37 - CLEARANCES - HOOD/

Page 87

246653-YTG-E-010888 Johnson Controls Unitary ProductsFIGURE 38 - PARTIAL ROOF CURB MODEL 1RC0455P8 3 . 0 08 7 . 0 03 8 . 5 99 5 . 0 92 6 . 0 02 3 5 .

Page 88

246653-YTG-E-0108Johnson Controls Unitary Products 89GUIDE SPECIFICATIONS - YORK MILLENNIUM 25, 30, & 40 TON UNITSGENERALUnits shall be manufactur

Page 89 - GUIDE SPECIFICATIONS - YORK

246653-YTG-E-0108Johnson Controls Unitary Products 9NOMENCLATURE123 4CONTROLADDITIONALD = SYNTHESYS CONTROLCONFIGURATIONVOLTAGEE = SYNTHESYS CONTROL,

Page 90 - HEATING SYSTEM (OPTIONAL)

246653-YTG-E-010890 Johnson Controls Unitary Productsshall be selected for a minimum service factor of 1.2 andhave fixed pitched sheaves. AIR FILTERI

Page 91 - REFRIGERATION SYSTEM

246653-YTG-E-0108Johnson Controls Unitary Products 91through each tube, to expel the flue gas and to maintain anegative pressure within the heat excha

Page 92 - CONTROLS

246653-YTG-E-010892 Johnson Controls Unitary Productsto allow complete drainage. Coils in excess of 48 inches highshall have an intermediate drain pan

Page 93 - COMFORT CONTROL FEATURES

246653-YTG-E-0108Johnson Controls Unitary Products 93The control shall lock on the Fan if the high temperature limittrips three times in one hour of o

Page 94

246653-YTG-E-010894 Johnson Controls Unitary ProductsThe control will use a Wall Sensor that has a warmer/coolerdial so the occupants can offset the p

Page 95 - AVAILABLE ACCESSORIES

246653-YTG-E-0108Johnson Controls Unitary Products 95OPTIONAL CONTROLYork Commercial Comfort System (YCCS)Provides rooftop system integration for YCCS

Page 96 - Norman, OK 73069

Subject to change without notice. Printed in U.S.A. 246653-YTG-E-0108Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 2466