York Y33 User Manual Page 53

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 52
246653-YTG-E-0108
Johnson Controls Unitary Products 53
4. Shaded RPMs require Class II blower.
A
IRFLOW (CFM)
A
VAILABLE EXTERNAL STATIC PRESSURE (IWG)
4.2 4.4 4.6 4.8 5.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
4000 1601 4.6 1636 4.9 1672 5.2 1707 5.5 1740 5.8
5000 1621 5.3 1656 5.6 1691 5.9 1725 6.2 1758 6.5
6000 1653 6.1 1687 6.4 1720 6.7 1753 7.0 1785 7.4
7000 1698 7.0 1730 7.3 1761 7.7 1792 8.0 1822 8.4
8000 1754 8.0 1784 8.4 1814 8.8 1843 9.1 1872 9.5
9000 1822 9.3 1850 9.7 1877 10.0 1905 10.4 1932 10.8
10000 1898 10.7 1924 11.1 1950 11.5 1976 11.9 2001 12.3
11000 1982 12.3 2006 12.7 2030 13.1 2054 13.6 2078 14.0
12000 2072 14.1 2095 14.6 2117 15.0 2140 15.5 2162 15.9
13000 2167 16.2 2188 16.7 2210 17.2 2231 17.7 2252 18.2
14000 2265 18.6 2286 19.1 2306 19.6 2326 20.1 2346 20.6
15000 2368 21.1 2387 21.7 2406 22.2 2425 22.8 2444 23.3
A
IRFLOW (CFM)
A
VAILABLE EXTERNAL STATIC PRESSURE (IWG)
5.2 5.4 5.6 5.8 6.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
4000 1774 6.1 1807 6.4 1838 6.7 1870 7.0 1902 7.3
5000 1791 6.8 1823 7.1 1855 7.5 1886 7.8 1917 8.1
6000 1817 7.7 1847 8.0 1878 8.4 1909 8.7 1938 9.1
7000 1853 8.7 1883 9.1 1912 9.4 1941 9.8 1970 10.2
8000 1901 9.9 1928 10.2 1956 10.6 1984 11.0 2012 11.4
9000 1958 11.2 1985 11.6 2012 12.0 2038 12.4 2064 12.8
10000 2026 12.7 2051 13.1 2076 13.6 2101 14.0 2125 14.4
11000 2102 14.5 2126 14.9 2149 15.3 2172 15.8 2196 16.3
12000 2185 16.4 2207 16.9 2229 17.4 2251 17.9 2273 18.3
13000 2273 18.6 2294 19.1 2315 19.6 2336 20.1 2356 20.6
14000 2366 21.1 2386 21.6 2406 22.1 2425 22.6 2445 23.2
15000 2463 23.8 2482 24.4 2501 24.9
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.
3.
BHP includes drive losses.
TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL