R-410AZF SERIES 15 - 25 Ton60 Hertz 853632-YIM-B-0213TABLE OF CONTENTSGeneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
853632-YIM-B-021310 Johnson Controls Unitary ProductsFigure 6: ZF180-300 Unit Dimensions Rear ViewNOTE: Units are shipped with the bottom duct openin
853632-YIM-B-0213Johnson Controls Unitary Products 11Figure 7: ZF180-300 Unit Dimensions Rain HoodNote: ELEC/ELEC Models: Units and ductwork are appro
853632-YIM-B-021312 Johnson Controls Unitary ProductsFigure 8: ZF180 Roof CurbFigure 9: ZF210-300 Roof CurbDuctworkDuctwork should be designed and siz
853632-YIM-B-0213Johnson Controls Unitary Products 13amounts of outdoor air intake on units that are not provided with an economizer or a motorized da
853632-YIM-B-021314 Johnson Controls Unitary ProductsProcedures which risk oil leakage include, but are not limited to, compressor replacement, repair
853632-YIM-B-0213Johnson Controls Unitary Products 15Figure 12: Field Wiring Disconnect - Cooling Unit With/Without Electric HeatThermostat WiringThe
853632-YIM-B-021316 Johnson Controls Unitary ProductsFigure 13: Typical Field Wiring 24 Volt ThermostatW1W2Y1GOCCPP1Y2XRSDCCSDSDROCCCRCGY2Y1W2W1Jumper
853632-YIM-B-0213Johnson Controls Unitary Products 17Table 8: Electrical Data ZF180-300 - Standard Drive Without Powered Convenience Outlet Size(Tons
853632-YIM-B-021318 Johnson Controls Unitary Products300(25)TBD TBD TBD TBD TBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD T
853632-YIM-B-0213Johnson Controls Unitary Products 19ZF180-300 - Standard Drive With Powered Convenience Outlet Size(Tons)VoltCompressors(each)OD Fan
853632-YIM-B-02132 Johnson Controls Unitary ProductsGeneralYORK® Model ZF units are either single package air conditions equipped with optional factor
853632-YIM-B-021320 Johnson Controls Unitary Products300(25)TBD TBD TBD TBD TBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD T
853632-YIM-B-0213Johnson Controls Unitary Products 21ZF180-300 - Hi Static Drive Without Powered Convenience Outlet Size(Tons)VoltCompressors(each)OD
853632-YIM-B-021322 Johnson Controls Unitary Products300(25)TBD TBD TBD TBD TBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD T
853632-YIM-B-0213Johnson Controls Unitary Products 23ZF180-300 - Hi Static Drive With Powered Convenience Outlet Size(Tons)VoltCompressors(each)OD Fa
853632-YIM-B-021324 Johnson Controls Unitary Products300(25)TBD TBD TBD TBD TBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD TBD TBD TBD TBD TBDTBD T
853632-YIM-B-0213Johnson Controls Unitary Products 25ZF180-300 - Low Static Drive Without Powered Convenience Outlet Size(Tons)VoltCompressors(each)O
853632-YIM-B-021326 Johnson Controls Unitary ProductsTable 9: ZF180-300 Physical Data ComponentModelsZF180 ZF210 ZF240 ZF300Nominal Tonnage 15 17.5 2
853632-YIM-B-0213Johnson Controls Unitary Products 27Optional Electric HeatThe factory-installed heaters are wired for single point power supply. Powe
853632-YIM-B-021328 Johnson Controls Unitary ProductsOptional Gas HeatThese gas-fired heaters have aluminized-steel or optional stainless steel, tubul
853632-YIM-B-0213Johnson Controls Unitary Products 29Gas ConnectionThe gas supply line can be routed within the space and roof curb, exiting through t
853632-YIM-B-0213Johnson Controls Unitary Products 3Wear safety glasses and work gloves. Use quenching cloth and have a fire extinguisher available du
853632-YIM-B-021330 Johnson Controls Unitary ProductsCheck all connections for leaks when piping is completed using a soap solution. NEVER USE A FLAME
853632-YIM-B-0213Johnson Controls Unitary Products 31module) to the “A”, “B”, “C” or “D” setting corresponding to the lettered curve of the Enthalpy S
853632-YIM-B-021332 Johnson Controls Unitary Products• OH - a 0-10 VDC analog input provided by a field-installed outdoor air relative humidity sensor
853632-YIM-B-0213Johnson Controls Unitary Products 33BAS-Ready VFDFactory-installed VFD is also available with 'BAS-ready' models. Terminal
853632-YIM-B-021334 Johnson Controls Unitary ProductsFigure 17: Enthalpy Set Point ChartFigure 18: Honeywell Economizer Control W721240(4)70(21)50(10)
853632-YIM-B-0213Johnson Controls Unitary Products 35PhasingYork® Model ZF units are properly phased at the factory. Check for proper compressor rotat
853632-YIM-B-021336 Johnson Controls Unitary ProductsFigure 20: Altitude/Temperature Correction FactorsThe examples below will assist in determining t
853632-YIM-B-0213Johnson Controls Unitary Products 37Drive Selection1. Determine side or bottom supply duct application.2. Determine desired airflow3.
853632-YIM-B-021338 Johnson Controls Unitary ProductsTable 15: Air Flow Performance - Side Duct ApplicationZF180 (15 Ton) Side DuctAir Flow(CFM)Availa
853632-YIM-B-0213Johnson Controls Unitary Products 39ZF240 (20 Ton) Side DuctAir Flow(CFM)Available External Static Pressure - IWG11. Blower performan
853632-YIM-B-02134 Johnson Controls Unitary ProductsNomenclatureZ F 180 N24 A 2 A AA 2 0 1 2 4 AZ = A/C, Single Pkg., R-410AProduct CategoryAirflow2 =
853632-YIM-B-021340 Johnson Controls Unitary ProductsZF300 (25 Ton) Side DuctAir Flow(CFM)Available External Static Pressure - IWG10.4 0.6 0.8 1.0 1.2
853632-YIM-B-0213Johnson Controls Unitary Products 41Table 16: Air Flow Performance - Bottom Duct ApplicationZF180 (15 Ton) Bottom DuctAir Flow(CFM)Av
853632-YIM-B-021342 Johnson Controls Unitary ProductsZF240 (20 Ton) Bottom DuctAir Flow(CFM)Available External Static Pressure - IWG11. Blower perform
853632-YIM-B-0213Johnson Controls Unitary Products 43ZF300 (25 Ton) Bottom DuctAir Flow(CFM)Available External Static Pressure - IWG10.4 0.6 0.8 1.0 1
853632-YIM-B-021344 Johnson Controls Unitary ProductsAir BalanceStart the supply air blower motor. Adjust the resistances in both the supply and the r
853632-YIM-B-0213Johnson Controls Unitary Products 45Figure 21: Pressure Drop Across A Dry Indoor Coil Vs. Supply Air CFM For All Unit Tonnages4. Know
853632-YIM-B-021346 Johnson Controls Unitary ProductsOperationCooling Sequence Of OperationFor ZF units, the thermostat makes a circuit between “R” an
853632-YIM-B-0213Johnson Controls Unitary Products 473. Freenet USB adapter driver, (http://www.yorkupg.com/software.asp)4. Simplicity® Freenet USB Ad
853632-YIM-B-021348 Johnson Controls Unitary Products• Single Enthalpy (optional): A field-installed, Outdoor Air Humidity sensor is connected to the
853632-YIM-B-0213Johnson Controls Unitary Products 49for cooling is still present at the conclusion of the ASCD, the UCB will re-energize the halted c
853632-YIM-B-0213Johnson Controls Unitary Products 5InstallationInstallation Safety InformationRead these instructions before continuing this applianc
853632-YIM-B-021350 Johnson Controls Unitary ProductsNOTE: All 240 & 480V heaters are provided with manual reset backup protection limits. These
853632-YIM-B-0213Johnson Controls Unitary Products 51When the thermostat calls for the first stage of heating, the low-voltage control circuit from “R
853632-YIM-B-021352 Johnson Controls Unitary ProductsIf voltage has been sensed at the GV for at least 15 seconds during the fan on delay for heating
853632-YIM-B-0213Johnson Controls Unitary Products 53Start-Up (Cooling)Prestart Check ListAfter installation has been completed:1. Check the electrica
853632-YIM-B-021354 Johnson Controls Unitary ProductsChecking Gas Heat Input1. Turn off all other gas appliances connected to the gas meter.2. With th
853632-YIM-B-0213Johnson Controls Unitary Products 55Adjustment Of Temperature RiseThe temperature rise (the difference of temperature between the ret
853632-YIM-B-021356 Johnson Controls Unitary ProductsCharging The UnitFigure 28: ZF180 (15 Ton) Charging ChartFigure 29: ZF210 (17.5 Ton) Charging Cha
853632-YIM-B-0213Johnson Controls Unitary Products 57TroubleshootingCooling Troubleshooting GuideOn calls for cooling, if the compressors are operatin
853632-YIM-B-021358 Johnson Controls Unitary Products7. If 24 volts is not present at the C1 terminal, check for 24 volts from the room thermostat at
853632-YIM-B-0213Johnson Controls Unitary Products 5924 volts is not present from the room thermostat, check for the following:a. 24 volts at the ther
853632-YIM-B-02136 Johnson Controls Unitary ProductsFigure 1: ZF180-300 Component LocationTable 1: ZF180-300 Unit LimitationsSize(Tons)Unit VoltageUni
853632-YIM-B-021360 Johnson Controls Unitary Productsfrom Y1 “OUT” for incorrect wiring. If 24 volts is not present at the Y1 “OUT” terminal, the UCB
853632-YIM-B-0213Johnson Controls Unitary Products 616. If 24 volts is not present at M3, check that 24 volts is present at the supply air blower moto
853632-YIM-B-021362 Johnson Controls Unitary Products3. Check the pilot orifice for obstruction as described in paragraph above. Clean as needed but t
853632-YIM-B-0213Johnson Controls Unitary Products 63Figure 32: Unit Control BoardTable 25: Unit Control Board Flash CodesFLASH CODEDESCRIPTIONGREENLE
Subject to change without notice. Printed in U.S.A. 853632-YIM-B-0213Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 8536
853632-YIM-B-0213Johnson Controls Unitary Products 7LocationUse the following guidelines to select a suitable location for these units:1. Unit is desi
853632-YIM-B-02138 Johnson Controls Unitary ProductsFigure 2: Unit 4 Point Load Weight Figure 3: Unit 6 Point Load WeightFigure 4: Center of GravityAB
853632-YIM-B-0213Johnson Controls Unitary Products 9Figure 5: ZF180-300 Unit Dimensions Front ViewNote: All entry holes should be sealed to prevent ra