York DPC-1 User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12
icon is displayed without flashing, whereas the , , and
icons are flashing. The temperature set point of this mode is
also displayed.
°C
If when moving one of the set points we come to less than
one degree from the following set point, it will be "dragged" so
as to avoid the unsuitability of the set points. When this hap-
pens, the thermostat will flash the icon of the occupation mode
of this set point being dragged.
The active keys are:
- Allow choosing between the heat and cool set points,
in each displaying the corresponding flashing icons
( or ).
- Allow changing the set point selected.
- Memorizes the two Economy set points and shows
the present set point that is not displayed at this
moment. In the case f dragged set points, all are
saved.
- Goes on to Programming Menu (back) without sav-
ing.
-
PROG
Pressing and holding allows recovering the factory
programmed Economy default values.
Programming unoccupied temperature set
points
Upon selecting the option on the programming menu, this
icon is displayed without flashing, whereas the , , and
icons are flashing. The temperature set point of this mode is
also displayed.
°C
If when moving one of the set points we come to less than
one degree from the following set point, it will be "dragged" so
as to avoid the unsuitability of the set points. When this hap-
pens, the thermostat will flash the icon of the occupation mode
of this set point being dragged.
The active keys are:
- Allow choosing between the heat and cool set points,
in each displaying the corresponding flashing icons
( or ).
- Allow changing the set point selected.
- Memorizes the two Unoccupied set points and shows
the present set point that is not displayed at this
moment. In the case f dragged set points, all are
saved.
- Goes on to Programming Menu (back) without sav-
ing.
-
PROG
Pressing and holding allows recovering the factory
programmed Unoccupied default values.
Thermostat in unoccupied mode
In any air conditioning mode, excluding the OFF mode, press-
ing the key for 1 second accesses the Setting Mode
and thermostat occupation is changed to Unoccupied.
If no other action is carried out, the unoccupied mode re-
mains indefinitely.
If the
PROG
key is pressed while in the Setting Mode, the
icon is displayed, the set point disappears and the No. 0 ap-
pears in its place, indicating the number of days the unoccu-
pied status should last. Keys and increase and
decrease this number of unoccupied days. If 0 is left this
status will remain indefinitely. If a number greater than 0 is
programmed, the icon will flash while this unoccupied sta-
tus remains, to indicate this is temporary. Once the unoccu-
pied status is concluded, and the number of programmed days
is over, the thermostat will change occupation to Day; but if
the air conditioning mode is AUTO PROG, this occupation
will depend upon the time schedule profile.
To exit this Unoccupied mode, just press the key.
Menu of supervising program
Entering the programming menu and pressing keys si-
multaneously, the first supervising menu will be displayed;
and pressing the
PROG
key the different submenus will ap-
pear on screen.
Submenus:
- Programming calibrations of temperature readings.
- Programming origin of temperature readings.
- Programming operating mode of the temperature control.
- Activation and deactivation of communication error readout.
- Selection of outdoor probe, analogue or digital.
Programming calibrations of temperature read-
ings
The first supervising submenu, P1, is the programming cali-
brations of temperature readings of the different origins of the
temperature value (different temperature probes).
P1 is displayed in clock digits, indicating Program 1, and S1,
S2, S3 or S4, indicating the probe selected.