Charging The Unit
Figure 31: ZR180 (15 Ton) Charging Chart
Figure 32: ZR240 (20 Ton) Charging Chart
15 Ton Charging Chart
250
300
350
400
450
500
550
125 130 135 140 145 150 155 160
Suction Pressure (psi)
Discharge Pressure (psi)
115º
105º
95º
85º
75º
Outdoor Tem
p(
ºF
)
1. Make sure that four condenser fans are running when charging. Two fans may switch off at a
lower temperatures (about 65 degrees).
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV’s have been
adjusted in the field, the charging chart may no longer apply.
20 Ton Charging Chart
250
300
350
400
450
500
550
100 105 110 115 120 125 130 135 140 145 150 155 160
Suction Pressure (psi)
Discharge Pressure (psi)
115º
105º
95º
85º
75º
Outdoor Tem
p(
ºF
)
1. Make sure that four condenser fans are running when charging. Two fans may switch off at a
lower temperatures (about 65 degrees).
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV’s have been
adjusted in the field, the charging chart may no longer apply.