York ZR240 Specifications Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 61
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
275864-YIM-C-0910
Johnson Controls Unitary Products 29
BAS-Ready VFD
Factory-installed VFD is also available with 'BAS-ready'
models. Terminal blocks are provided in the control box (in
place of the VAV control board) for field wiring of a customer-
installed BAS to receive 24 VAC power and to connect to the
following control signals:
a duct static pressure transducer input signal (0-5 VDC)
an economizer actuator input signal (2-10 VDC)
an economizer actuator output signal (2-10 VDC)
a VFD speed reference output signal (2-10 VDC)
The use of shielded cable is recommended for the above
control wiring connections.
NOTE: Factory-installed VFD is not available with factory-
installed BAS options due to space limitations in the
control box.
A solid-state, lock-out relay (LR) and 100-F, 50 VDC capacitor
must be field-supplied and installed to provide a means to
transmit a potential fault signal back to the BAS controller. The
specific relay part number required will depend upon the need
for either AC-output or DC-output. See price pages for further
details.
Once the appropriate relay and capacitor are obtained, install
the capacitor across LR terminals '3' & '4' and make the
following wiring connections:
LR '1' to BAS controller
LR '2' to BAS controller
LR '3' to UCB 'X'
LR '4' to UCB 'C'
'VFD-Ready' For Customer-installation
Units configured as 'VFD-ready' provide provisions for a
customer-installed drive. The physical dimensions of VFDs can
vary greatly among manufacturers, horsepower ratings and
voltage requirements. Keep in mind that drive manufacturers
also require various minimum clearances to allow for adequate
internal cooling of the drive during operation.
The unit comes with a mounting bracket installed in the Blower
Access compartment which may accommodate other vendor's
drives depending on their size. In order to utilize the unit's
mounting bracket, the maximum recommended drive
dimensions are as follows:
For 5-hp motor applications ........................13" H x 6" W x 7" D
For 7.5 thru 15-hp motor applications.........13" H x 8" W x 8" D
If the drive will not fit in the allotted space, then it will need to be
mounted elsewhere; either within the building on a perpendicular
wall which is not subjected to excessive temperature, vibration,
humidity, dust, corrosive gas, explosive gas, etc., or within an
appropriate enclosure rated for outside installation to safeguard
against moisture, dust and excessive heat.
The power leads to the drive (L1, L2, L3) and from the motor
(T1, T2, T3) along with the respective ground wires are supplied
with the unit and need to be connected after the drive is
installed.
A terminal block located in the control box is provided for field
connection of the VFD speed reference signal (2-10 VDC) and
to the normally-open, run-permit auxiliary contact. The use of
shielded cable is recommended for the above control wiring
connections.
For VFD-ready units also equipped with gas/electric heat,
a terminal block located in the unit's control box and con
-
nected to the VAV board's "VAV BOX" terminal, must be
field wired to the building's VAV boxes to ensure fully
open dampers during heating operation.
Optional Hot Gas Bypass (HGBP)
To allow for low cooling load operation, a direct-acting,
pressure-modulating bypass control valve installed on the
system #1 discharge line is used to divert high temperature,
high pressure refrigerant around the TXV in order to maintain a
desired minimum evaporator pressure.
The opening pressure of the bypass valve is fully adjustable
between 0 and 80 psig with a factory-setting of 60 psig. HGBP
is standard on all units with VAV and optional with CV units.
If the unit is operated with the manual bypass switch in
the LINE (BYPASS) position and there are VAV boxes
present in the duct system, then boxes must be driven to
the full-open position using a customer-supplied power
source to prevent over-pressurizing and possible
damage to the ductwork.
Before beginning any service, disconnect all power to
the drive. Be aware that high voltages are present in the
drive even after power has been disconnected.
Capacitors within the drive must be allowed to discharge
before beginning service.
Do not connect AC power to the T1, T2, T3 drive
terminals to prevent damage to the VFD.
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 60 61

Comments to this Manuals

No comments