WATER SYSTEMS
62
System diagram
COMPACT
The Digital Scroll Compressor uses a simple
and effective method to modulate the capacity
of an AC, giving unparalleled performance in
the modulation field. To modulate the capacity
the Digital Scroll operates in two stages, the
"loaded state" in which the compressor works
as a normal Scroll compressor at full capacity
and mass flow, and the "unloaded state", where
there is not capacity and mass flow. During the
"unloaded state" there is a separation between
the scrolls. Once the scrolls separate, any gas
passing through is no longer compressed.
Changing the cycle time ("Loaded state" time
and "Unloaded state" time) determines the
capacity modulation of the compressor.
Modulation
chamber
Bleed hole
Lift piston
assembly
Solenoid
valve
Spring
Digital Scroll
Leaving water temperature down to -5°C possible
Capacity contro-
lled chiller
Fan coil unit (or any
other kind of water coil
Water piping max.
distance app. 150 m*
* Max. possible length depends on fan coil unit pressure drops and requested water flow rate.